Free interconnection of analog signals

Free configuration of analog outputs

10

l

333

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0419

v
(Cont.)

Possible analog signals for C0419

^ 332

0

Output frequency
(MCTRL1−NOUT+SLIP)

6 V/12 mA/5.85 kHz

º C0011

1

Device utilisation (MCTRL1−MOUT) at
V/f characteristic control (C0014 = 2 or
3)

3 V/6 mA/2.925 kHz

º rated active

inverter current (active
current/C0091)

Actual motor torque (MCTRL1−MACT)
with vector control (C0014 = 4) or
sensorless torque control (C0014 = 5)

3 V/6 mA/2.925 kHz

º rated

motor torque

2

Apparent motor current
(MCTRL1−IMOT)

3 V/6 mA/2.925 kHz

º rated

inverter current

3

DC−bus voltage (MCTRL1−DCVOLT)

6 V/12 mA/5.85 kHz

º DC 1000 V

(400 V mains)
6 V/12 mA/5.85 kHz

º DC 380 V

(230 V mains)

4

Motor power (MCTRL1−PMOT)

3 V/6 mA/2.925 kHz

º rated

motor power

5

Motor voltage (MCTRL1−VOLT)

4.8 V/9.6 mA/4.68 kHz

ºrated

motor voltage

6

1/output frequency (1/C0050)
(MCTRL1−1/NOUT)

2 V/4 mA/1.95 kHz

º 0.5 ´ C0011

7

Output frequency within adjusted
limits (DCTRL1−C0010...C0011)

0 V/0 mA/4 mA/0 kHz

º f = f

min

(C0010)
6 V/12 mA/5.85 kHz

º f = f

max

(C0011)

8

Operation with process controller
(C0238 = 0, 1):
Actual process controller value
(PCTRL1−ACT)

6 V/12 mA/5.85 kHz

º C0011

Operation without process controller
(C0238 = 2):
Output frequency without slip
(MCTRL1−NOUT)