Technical data

Operation with increased rated power
Rated data for 400 V mains voltage

4

l

56

EDS82EV903 EN 3.0

Typical motor power
Three−phase asynchronous
motor (4−pole)

P

rated

[kW]

4.0

5.5

11

P

rated

[hp]

5.0

7.5

15

8200 vector type

EMC filter integrated

E82xV302K4C0xx

E82xV402K4C0xx

2)

E82xV752K4C0xx

2)

Without EMC filter

E82xV302K4C4xx

E82xV402K4C2xx

2)

E82xV752K4C2xx

2)

Rated mains current

without mains choke

I

mains

[A]

10.8

with mains choke

I

mains

[A]

8.4

10.6

18.0

Output power +U

DC

, −U

DC

1)

P

DCres

[kW]

0.7

0

0

Rated output
current at
switching
frequency

2 kHz sin

I

r

[A]

8.7

11.4

19.8

4 kHz sin

Max. permissible
output current for
60 s at switching
frequency

2 kHz sin

I

max

[A]

11.0

14.2

24.8

4 kHz sin

Power loss (operation with
I

N24

)

E82EV...

P

loss

[W]

145

180

300

E82DV... inside/outside

P

loss

[W]

48/97

60/120

100/200

E82CV... inside/cooler

P

loss

[W]

48/97

60/120

100/200

Dimensions

Dependent on the mounting variant (

^ 61)

Mass

E82EV...

m [kg]

2.9

3.6

E82DV...

m [kg]

2.9

3.6

E82CV...

m [kg]

2.4

3.0

1)

Power supplied by the DC bus when operating with power−adapted motor

2)

Operation only permitted with mains choke (

^ 106)