Safety engineering

Operating mode

14

l

494

EDS82EV903 EN 3.0

Deactivating "Safe torque off"

An AND operation of the disconnecting paths prevents the drive from restarting if only one
disconnecting path is enabled.

"Safe torque off" is deactivated (output of pulses to the inverter is enabled) if there is a
HIGH level at both disconnecting paths.

)

Note!

8200 vector E82xV...x4x with application I/O − can only be used with one
disconnecting path:
Always switch the controller inhibit (terminal x3.3/28) together with safety
relay Ksr.
Otherwise the motor will start without acceleration ramp or with a shorter
acceleration ramp.