Code table

10

l

432

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0500
*

Calibration of
process
variable −
numerator

2000 1

{1}

25000

l

Codes C0010, C0011, C0017,
C0019, C0037, C0038, C0039,
C0044, C0046, C0049, C0050,
C0051, C0138, C0140, C0181,
C0239, C0625, C0626, C0627
can be calibrated in a way to
make the keypad display a
process variable

l

If C0500/C0501 are changed,
the "Hz" unit is not shown in
the display anymore

^ 362

C0501
*

Calibration of
process
variable −
denominator

10

1

{1}

25000

C0500
*
(A)

Calibration of
process
variable −
numerator

2000 1

{1}

25000

l

Codes C0037, C0038, C0039,
C0044, C0046, C0049, C0051,
C0138, C0140, C0181 can be
calibrated in a way to make the
keypad display a process
variable in the unit selected in
C0502

l

Frequency−dependent codes
such as C0010, C0011, C0017,
C0019, C0050, C0239, C0625,
C0626, C0627 are always
provided in "Hz"

l

Changes in codes C0500 and
C0501 affect codes C0010 and
C0011; their values are scaled
correspondingly in the process

^ 362

C0501
*
(A)

Calibration of
process
variable −
denominator

10

1

{1}

25000

C0502
*
(A)

Unit − process
variable

0

0: Ċ
1: ms
2: s
4: A
5: V

6: rpm
9: °C

10: Hz
11: kVA
12: Nm

13: %
14: kW
15: N
16: mV
17: m

W

18:

W

19: hex
34: m
35: h
42: mH

C0517
*

v

User menu

l

After mains switching or in the

g function the code from
C0517/1 is displayed.

l

In the Lenze setting the user
menu contains the most
important codes for
commissioning the operating
mode "V/f characteristic
control with a linear
characteristic"

l

If the password protection is
active, only the codes entered
in C0517 can be freely accessed

l

If less than 10 codes are
required, assign the value "0"
(zero) to the memory locations
not used. Please observe that
the software automatically
assigns code C0050 to a
memory location that is not
used, if it has not been
explicitly assigned to another
memory location.

^ 373

1 Memory 1

50

C0050

Output frequency (MCTRL1−NOUT)

2 Memory 2

34

C0034

Range of analog setpoint selection

3 Memory 3

7

C0007

Fixed configuration of digital input
signals

4 Memory 4

10

C0010

Minimum output frequency

5 Memory 5

11

C0011

Maximum output frequency

6 Memory 6

12

C0012

Acceleration time main setpoint

7 Memory 7

13

C0013

Deceleration time main setpoint

8 Memory 8

15

C0015

V/f rated frequency

9 Memory 9

16

C0016

V

min

boost

10 Memory 10

2

C0002

Parameter set transfer

Possible entries for C0517

xxxx

All codes apart from the codes labelled
with "(A)".

Syntax:
Codes: C0517/x = cccc
Subcodes: C0517/x = cccc.ss

C0518 Service codes

Alterations by Lenze service only!

C0519
C0520

C0597
*

v

Configuration −
motor phase
failure
detection

0

0

Inactive

1

TRIP error message

Keypad: LP1, bus: 32

2

Warning

Keypad: LP1, bus: 182

Advertising