2 fault messages, Fault messages, Troubleshooting and fault elimination – Lenze E82xVxxxKxxxxx User Manual

Page 456: Fault elimination fault messages

Advertising
background image

Troubleshooting and fault elimination

Fault elimination
Fault messages

11

l

456

EDS82EV903 EN 3.0

11.3.2

Fault messages

Keypad

PC

1)

Fault

Cause

Remedy

noer

0

No fault

ccr
a

71

System fault

Strong interference injections on the
control cables

Shield control cables

Earth loops in the wiring

ce0
a

61

Communication error
on AIF
(configurable in C0126)

Faulty transmission of control
commands via AIF

Insert the communication module firmly
into the diagnosis terminal

ce1
a

62

Communication error
on CAN−IN1 with sync
control

CAN−IN1 object receives faulty data, or
communication is interrupted

l

Check plug connection bus module

ó FIF

l

Check transmitter

l

Increase monitoring time in C0357/1, if
necessary

ce2
a

63

Communication error
on CAN−IN2

CAN−IN2 object receives faulty data, or
communication is interrupted

l

Check plug connection bus module

ó FIF

l

Check transmitter

l

Increase monitoring time in C0357/2, if
necessary

ce3
a

64

Communication error
on CAN−IN1 with event
or time control

CAN−IN1 object receives faulty data, or
communication is interrupted

l

Check plug connection bus module

ó FIF

l

Check transmitter

l

Increase monitoring time in C0357/3, if
necessary

ce4
a

65

BUS−OFF
(many communication
errors occurred)

Controller has received too many faulty
telegrams via the system bus and has
been disconnected from the bus

l

Check bus termination

l

Check shield connection of the cables

l

Check PE connection

l

Check bus load, reduce the baud rate, if
necessary

ce5
a

66

CAN time−out
(configurable in C0126)

For remote parameterisation via the
system bus (C0370):
Slave does not respond.
Communication monitoring time has
been exceeded

l

Check wiring of the system bus

l

Check system bus configuration

For operation with application I/O:
Parameter set change−over has been
parameterised incorrectly

The "parameter set change−over" signal
(C0410/13, C0410/14) must be connected to
the same source in all parameter sets

For operation with module on FIF:
Internal error

Contact Lenze

ce6
a

67

System bus (CAN)
function module on FIF
has the "Warning" or
"BUS−OFF" status
(configurable in C0126)

CAN controller reports "Warning" or
"BUS−OFF" status

l

Check bus termination

l

Check shield connection of the cables

l

Check PE connection

l

Check bus load, reduce the baud rate, if
necessary

ce7
a

68

Communication error
during remote
parameterisation via
system bus (C0370)
(configurable in C0126)

Node does not respond or is not
available

l

Check bus termination

l

Check shield connection of the cables

l

Check PE connection

l

Check bus load, reduce the baud rate, if
necessary

For operation with application I/O:
Parameter set change−over has been
parameterised incorrectly

The "parameter set change−over" signal
(C0410/13, C0410/14) must be connected to
the same source in all paramerter sets

EEr
a

91

External fault (TRIP−SET) A digital signal assigned to the TRIP−Set

function is activated

Check external encoder

ErP0
...
ErP19
a

Communication abort
between keypad and
standard device

Various

Contact Lenze