Electrical installation

Standard devices in a power range from 3 ... 11 kW

EMC−compliant wiring

6

l

131

EDS82EV903 EN 3.0

6.5

Standard devices in a power range from 3 ... 11 kW

6.5.1

EMC−compliant wiring

(Design of a CE−typical drive system)

The drives comply with the EC Directive on "Electromagnetic Compatibility" if they are
installed in accordance with the specifications for the CE−typical drive system. The user is
responsible for the compliance of the machine application with the EC Directive.

)

Note!

ƒ

Control cables and mains cables must be separated from the motor cable to
avoid interference injections.

ƒ

Always use shielded control cables.

ƒ

Generally we recommend to shield the cable for the PTC or thermal contact
and route it separately from the motor cable.

ƒ

If you route the cores for the motor connection and the cores for the
connection of the PTC or thermal contact within one cable with a common
shield:
– To reduce interference injections on the PTC cable we recommend to

additionally install the PTC kit type E82ZPEx.

ƒ

Optimum HF shield connection of the motor cable is obtained by using the
terminal

2for motor PE and motor shield.