Function library
Parameter set management
Saving and copying parameter sets
l
370
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0003
*
v
Saving
parameters
non−volatilely
1
0
Do not save parameters in the EEPROM Data loss after mains switch−off
1
Always save parameters in the EEPROM
l
Active after every mains
connection
l
Cyclic alteration of parameters
via bus module is not
permissible
3
Save your own basic setting in the
EEPROM
Afterwards save parameter set 1
as own basic setting with
C0002 = 9
)
Note!
ƒ
Do not remove keypad as long as the parameters are being transmitted! If
the keypad is removed during transmission, the controller indicates the
errors "Prx" or "PT5".
ƒ
A detailed description of the keypads can be found in the "Parameter
setting" chapter.
Restoring the delivery status
1. Attach keypad.
2. Inhibit controller with
s or via terminal (X3/28 = LOW).
3. Set the correct selection number in C0002 from the "Restore delivery status"
category and confirm with
v.
– E.g. C0002 = 1: Parameter set 1 of the controller is overwritten with Lenze setting.
Parameter set transfer from the controller to the keypad
1. Attach keypad.
2. Inhibit controller with
s or via terminal (X3/28 = LOW).
3. Set C0002 = 20 or 50 or 80, confirm with
v.
Parameter set transfer from the keypad to the controller
1. Attach keypad.
2. Inhibit controller with
s or via terminal (X3/28 = LOW).
3. Set the correct selection number In C0002 from the "Parameter set transfer with
keypad" category and confirm with
v.
– E.g. C0002 = 10: All parameter sets of the controller are overwritten with the
settings in the keypad.
– E.g. C0002 = 11: Parameter set 1 of the controller is overwritten with the settings
in the keypad.