Function library

Current−limit controller

10

l

327

EDS82EV903 EN 3.0

10.10

Current−limit controller

Description

For controlling high moments of inertia the current limiting controller (I

max

controller) can

be set.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0077
*

Gain of the
I

max

controller

0.25

0.00
= P component
inactive

{0.01}

16.00

^ 327

C0078
*

Reset time of
the I

max

controller

65

à

13
0

12

{1 ms}

9990

= I component

inactive

à

Only 8200 vector 15 ... 90 kW)

^ 327

Adjustment

The current limiting controller is factory−set so that the drive is stable.

Setting notes for power control

The current limiting controller must only be adapted in case of a power control with high
moments of inertia:

ƒ

V/f characteristic control (C0014 = 2 or 3)

ƒ

V

P

(C0077):

» 0.06

ƒ

T

i

(C0078):

» 750 ms

)

Note!

C0077 and C0078 are the same for all parameter sets.