Function library – Lenze E82xVxxxKxxxxx User Manual

Page 403

Advertising
background image

Function library

Code table

10

l

403

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0235
*
(A)

Differential
threshold
PCTRL1−SET=
ACT

0.00

0.00

{0.01

Hz}

650.00 Operating threshold of digital

output signal PCTRL1−SET=ACT
(process controller setpoint =
actual process controller value)

l

If the difference between
PCTRL1−SET and PCTRL1−ACT is
within C0235:
– PCTRL1−SET=ACT = HIGH

after expiration of the time
set in C0234

C0236
(A)

Acceleration
time − lower
frequency
limitation

0.00

0.00

{0.02 s}

1300.00 Based on C0011

Lower frequency limitation =
C0239

^ 281

C0238

v

Frequency
precontrol

2

0

No feedforward control (only process
controller)

Process controller has full
influence

^ 318

^ 322

1

Feedforward control (overall setpoint +
process controller)

Process controller has restricted
influence

2

No feedforward control (overall
setpoint only)

Process controller does not have
any influence (inactive)

Overall setpoint (PCTRL1−SET3) =
main setpoint + additional
setpoint

C0239 Lower

frequency
limitation

−650.0

0

−650.00

{0.02

Hz}

650.00

l

The value does not fall below
the limit independently of the
setpoint

l

If the lower frequency
limitation is active, automatic
DC injection braking (auto
DCB) must be deactivated with
C0019 = 0 or C0106 = 0

^ 281

C0240

v

(A)

Invert process
controller
output
(PCTRL1−INV−
ON)
(parameter
channel)

0

0

Not inverted

Set digital signal PCTRL1−INV−ON
(invert process controller output)
via keypad/PC or parameter
channel

1

Inverted

C0241

v

(A)

Fade−in/fade−
out process
controller
(PCTRL1−
FADING)
(parameter
channel)

0

0

Fade−in process controller

Set digital signal PCTRL1−FADING
(fade−in/fade−out process
controller) via keypad/PC or
parameter channel

1

Fade−out process controller

C0242

v

(A)

Activate
inverted
control for
process
controller

0

0

Regular control

Actual value increases

ð output

frequency increases

1

Inverted control

Actual value increases

ð output

frequency decreases

C0243

v

(A)

Deactivate
additional
setpoint
(PCTRL1−NADD
−OFF)
(parameter
channel)

0

0

PCTRL1−NADD active

Set digital signal
PCTRL1−NADD−OFF (activate
additional setpoint) via keypad/PC
or parameter channel

1

PCTRL1−NADD inactive

C0244

v

(A)

Root function
for actual
process
controller
value

0

0

Inactive

1

" | PCTRL1−ACT |

Ǹ

Internal computing method:
1. Save sign of PCTRL1−ACT
2. Extract the root of the amount
3. Multiply result by the sign