Function library – Lenze E82xVxxxKxxxxx User Manual
Page 403
![background image](/manuals/566070/403/background.png)
Function library
Code table
l
403
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0235
*
(A)
Differential
threshold
PCTRL1−SET=
ACT
0.00
0.00
{0.01
Hz}
650.00 Operating threshold of digital
output signal PCTRL1−SET=ACT
(process controller setpoint =
actual process controller value)
l
If the difference between
PCTRL1−SET and PCTRL1−ACT is
within C0235:
– PCTRL1−SET=ACT = HIGH
after expiration of the time
set in C0234
C0236
(A)
Acceleration
time − lower
frequency
limitation
0.00
0.00
{0.02 s}
1300.00 Based on C0011
Lower frequency limitation =
C0239
^ 281
C0238
v
Frequency
precontrol
2
0
No feedforward control (only process
controller)
Process controller has full
influence
^ 318
^ 322
1
Feedforward control (overall setpoint +
process controller)
Process controller has restricted
influence
2
No feedforward control (overall
setpoint only)
Process controller does not have
any influence (inactive)
Overall setpoint (PCTRL1−SET3) =
main setpoint + additional
setpoint
C0239 Lower
frequency
limitation
−650.0
0
−650.00
{0.02
Hz}
650.00
l
The value does not fall below
the limit independently of the
setpoint
l
If the lower frequency
limitation is active, automatic
DC injection braking (auto
DCB) must be deactivated with
C0019 = 0 or C0106 = 0
^ 281
C0240
v
(A)
Invert process
controller
output
(PCTRL1−INV−
ON)
(parameter
channel)
0
0
Not inverted
Set digital signal PCTRL1−INV−ON
(invert process controller output)
via keypad/PC or parameter
channel
1
Inverted
C0241
v
(A)
Fade−in/fade−
out process
controller
(PCTRL1−
FADING)
(parameter
channel)
0
0
Fade−in process controller
Set digital signal PCTRL1−FADING
(fade−in/fade−out process
controller) via keypad/PC or
parameter channel
1
Fade−out process controller
C0242
v
(A)
Activate
inverted
control for
process
controller
0
0
Regular control
Actual value increases
ð output
frequency increases
1
Inverted control
Actual value increases
ð output
frequency decreases
C0243
v
(A)
Deactivate
additional
setpoint
(PCTRL1−NADD
−OFF)
(parameter
channel)
0
0
PCTRL1−NADD active
Set digital signal
PCTRL1−NADD−OFF (activate
additional setpoint) via keypad/PC
or parameter channel
1
PCTRL1−NADD inactive
C0244
v
(A)
Root function
for actual
process
controller
value
0
0
Inactive
1
" | PCTRL1−ACT |
Ǹ
Internal computing method:
1. Save sign of PCTRL1−ACT
2. Extract the root of the amount
3. Multiply result by the sign