DC−bus operation

Conditions for trouble−free DC−bus operation

Possible combinations of Lenze controllers in a network of several drives

12

l

461

EDS82EV903−3.0

12.3.1

Possible combinations of Lenze controllers in a network of several drives

Combinations in the 230 V mains

Type

Data

E82xVxxxK2C

E82xVxxxK2C



3 / PE / AC / 100 V − 0 % ... 264 V + 0%

45 Hz − 0 % ... 65 Hz + 0 %

‚

DC 140 V ... 370 V

ƒ

DC 380 V

Combinations in the 400 V mains

Type

Data

E82xVxxxK4x

93xx

E82xVxxxK4x



3 / PE / AC / 320 V − 0 % ... 440 V + 0 %

45 Hz − 0 % ... 65 Hz + 0 %

93xx

‚

DC 460 V ... 620 V

ƒ

DC 725 V

 max. permissible range mains voltage

‚ permissible range DC−bus voltage

ƒ switching threshold of the braking unit

12.3.2

Mains connection

Cable protection and cable cross−section

Dimension the mains fuses and the cable cross−section of the mains cables for the mains
current resulting from the maximum supply power P

DC100%

. Additional basic conditions

such as local regulations, temperatures, etc. must also be observed. (

467)

)

Note!

An asymmetrical DC−bus system may require higher dimensioning by factor
1.35 ... 1.5.

Mains current

Rule of thumb for the mains current in a DC−bus system:

I

Netz

[A] [

P

DC100%

[W]

1.6 @ U

Netz

[V]

Mains chokes. EMC

The application of mains chokes limits and proportionally allots the current and the power
of the mains input circuits of the controllers (depending on their performance).

Only use mains chokes that are specified for DC−bus operation. (

465)

)

Note!

Please observe that the DC−bus operation may require different mains chokes,
mains fuses and cable cross−sections than the individual operation.
Compliance with the EMC Directive may not be ensured. Check the application
of central interference suppression (collective filter) in the AC supply.