Function library – Lenze E82xVxxxKxxxxx User Manual

Page 429

Advertising
background image

Function library

Code table

10

l

429

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0423
*
(A)

Delay of digital
outputs

0.000

{0.001 s}

65.000 "Debouncing" of the digital

outputs
(from version: application I/O
E82ZAFA ... Vx11)

l

Switches the digital output if
the linked signal is still active
after the time set.

l

The digital output is reset
without delay

^ 348

1 Device version

151:
relay output K1
(RELAY)
Device version
152, 153:
Digital
switching
output K1

0.000

2 Digital output

X3/A1
(DIGOUT1)

0.000

3 Digital output

X3/A2
(DIGOUT2)

0.000

C0424
*

v

(A)

Output signal
range − analog
outputs
Application I/O

0
1

0 ... 10 V / 0 ... 20 mA
4 ... 20 mA

Observe jumper position of the
function module!
(from version: application I/O
E82ZAFA ... Vx11)

^ 332

1 X3/62 (AOUT1)

0

2 X3/63 (AOUT2)

0

Advertising