3 optimising the operating behaviour, 1 slip compensation, Slip compensation – Lenze E82xVxxxKxxxxx User Manual

Page 268: Function library

Advertising
background image

Function library

Optimising the operating behaviour
Slip compensation

10

l

268

EDS82EV903 EN 3.0

10.3

Optimising the operating behaviour

10.3.1

Slip compensation

Description

Under load, the speed of an asynchronous machine is reduced. This load dependent speed
drop is called slip. The slip can be partly compensated by setting C0021 accordingly. The slip
compensation is effective for all control modes (C0014).

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0021 Slip

compensation

0.0

−50.0

{0.1 %}

50.0 C0021 is calculated and saved

during the motor parameter
identification with C0148.

^ 268

Automatic adjustment

The slip compensation is calculated during the motor parameter identification and
entered under C0021.

Preparing motor parameter identification

You must enter the motor data of the motor nameplate:

ƒ

Rated motor speed (C0087)

ƒ

Rated motor current (C0088)

ƒ

Rated motor frequency (C0089)

ƒ

Rated motor voltage (C0090)

ƒ

Motor cos

j (C0091)

Motor parameter identification

Carry out the motor parameter identification. (

^ 315

)

Automatically detected parameters

V/f−rated frequency (C0015), slip compensation (C0021) and motor stator inductivity
(C0092) are calculated and saved. The total resistance of motor cable and motor is
measured and saved as motor stator resistance (C0084).