Electrical installation – Lenze E82xVxxxKxxxxx User Manual

Page 164

Advertising
background image

Electrical installation

Standard devices in the power range 75 ... 90 kW
Connection relay outputs K1 and K2

6

l

164

EDS82EV903 EN 3.0

Relay K2

Function

Relay position

switched

Message

(Lenze setting)

Technical data

X1.3/K21

Relay output
normally−closed
contact

opened

not assigned

AC 250 V/3 A

DC 24 V/2 A ... DC 240 V/0.22 A

X1.3/K22

Relay mid−position
contact

X1.3/K24

Relay output
normally−open
contact

closed

not assigned

PES

HF shield termination by PE connection through shield clamp

)

Note!

ƒ

Switching of control signals:
– Use shielded cables
– HF shield termination by PE connection
– The minimum load for switching the signals through correctly is 12 V and

5 mA. Both values have to be exceeded at the same time.

ƒ

Switching of mains potentials:
– Unshielded cables are sufficient

ƒ

For the protection of the relay contacts a corresponding suppressor circuit is
absolutely required for an inductive or a capacitive load!

ƒ

The service life of the relay depends on the type of load (ohmic, inductive or
capacitive) and the value of the switching capacity.

ƒ

The output message can be changed with C0409.

ƒ

If you use an application I/O function module:
– The relay K2 is only active with application I/O E82ZAFAC from version

Vx21 onwards.