Function library

Configuration of analog and digital setpoints and actual values

Digital setpoints via frequency input

10

l

303

EDS82EV903 EN 3.0

Example: Calibration when using a process controller

Example for pressure control

The control range of a pressure control is to be limited to a value lower than the rated
sensor value P

rated

. For this purpose, the effective pressure setpoint can be proportionally

reduced through the gain of the analog input (C0027, C0414):

ƒ

Actual pressure value via pressure sensor (P

N

= 0 − 200 mbar) at X3/2U

(C0412/5 = 4).

ƒ

Analog pressure setpoint via X3/1U (C0412/4 = 1).

ƒ

The maximum pressure is to be limited to 120 mbar. Reduce the effective pressure
setpoint via the gain of the analog input.

C0414ń1 +

P

1

P

N

@ 100 % + 120 mbar

200 mbar @ 100 % + 60 %

10.7.3

Digital setpoints via frequency input

Description

Digital inputs E1 and E2 of the standard I/O or the application I/O can be configured as
frequency inputs. That way, a digital frequency can be selected as setpoint or actual value:

ƒ

When operating with standard I/O:
– Single−track: 0 ... 10 kHz at X3/E1
– Two−track: 0 ... 1 kHz at X3/E1 and X3/E2

ƒ

When operating with application I/O
– Single−track: 0 ... 102.4 kHz at X3/E1
– Two−track: 0 ... 102.4 kHz at X3/E1 and X3/E2