Function library, Code table – Lenze E82xVxxxKxxxxx User Manual
Page 385
![background image](/manuals/566070/385/background.png)
Function library
Code table
l
385
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0008
v
Fixed
configuration −
relay output K1
(relay, motec
version 151) or
Digital
switching
output K1
(motec
versions 152,
153)
1
Change of C0008 is copied into
C0415/1. Free configuration in
C0415/1 sets C0008 = 255!
^ 348
0
Ready for operation (DCTRL1−RDY)
1
TRIP error message (DCTRL1−TRIP)
2
Motor is running (DCTRL1−RUN)
3
Motor is running / CW rotation
(DCTRL1−RUN−CW)
4
Motor is running / CCW rotation
(DCTRL1−RUN−CCW)
5
Output frequency = 0
(DCTRL1−NOUT=0)
6
Frequency setpoint reached
(DCTRL1−RFG1=NOUT)
7
Values have fallen below frequency
threshold Q
min
(f < C0017)
(PCTRL1−QMIN)
LOW active
8
I
max
limit reached (MCTRL1−IMAX)
C0014 = 5: torque setpoint reached
9
Overtemperature (
ϑ
max
−5 °C)
(DCTRL1−OH−WARN)
10
Values have fallen below TRIP or Q
min
or pulse inhibit (IMP)
(DCTRL1−TRIP−QMIN−IMP)
11
PTC warning (DCTRL1−PTC−WARN)
12
Apparent motor current < current
threshold (DCTRL1−IMOT<ILIM)
V−belt monitoring
Apparent motor current = C0054
Current threshold = C0156
Frequency threshold Q
min
= C0017
13
Apparent motor current < current
threshold and output frequency >
Frequency threshold Q
min
(DCTRL1−(IMOT<ILIM)−QMIN)
14
Apparent motor current < current
threshold and ramp function generator
1: input = output
(DCTRL1−(IMOT<ILIM)−RFG1=0)
15
Motor phase failure warning
(DCTRL1−LP1−WARN)
16
Minimum output frequency reached
(f
£ C0010) (PCTRL1−NMIN)
LOW active
255
Free configuration in C0415/1
Read only
Do not change C0008 since
settings in C0415/1 may get lost
C0009
*
v
Device address
1
1
{1}
99 Only for communication modules
on the AIF interface:
l
LECOM−A (RS232) E82ZBL
l
LECOM−A/B/LI 2102
l
PROFIBUS−DP 213x,
l
System bus (CAN) 217x
Set the node address for
operation with system bus
function module E82ZAFCC in
C0350.