IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0174
*
s
Switching
threshold −
brake chopper
100
78
{1 %}
110 Only active with 8200 motec 3 ...
7.5 kW and 8200 vector
0.55 ... 11 kW, version for
400/500 V mains voltage
l
100 % = switching threshold
DC 790 V
l
110 % = brake chopper
switched off
l
U
DC
= switching threshold in V
DC
l
The recommended setting
considers max. 10 % mains
overvoltage
^ 484
Required setting
U
mains
[3/PE AC xxx V]
380
400
415
440
460
480
500
C0174
[%]
78
81
84
89
93
97
100
U
DC
[V DC]
618
642
665
704
735
767
790
C0178
*
Operating
hours
{h}
Read only
Total time − terminal 28 (CINH) =
HIGH
C0179
*
Power−on time
{h}
Read only
Total time of mains "ON"
C0181
*
Process
controller
setpoint 2
(PCTRL1−SET2)
0.00
−650.00
{0.02
Hz}
650.00
^ 322
C0182
*
Integration
time − S−ramps
0.00
0.00
{0.01 s}
50.00
l
C0182 = 0.00: ramp function
generator operates linearly
l
C0182 > 0.00: ramp function
generator operates in an
S−shape (without jerk)
^ 286
C0183
*
Diagnostics
0
No fault
Read only
102
TRIP active
104
Message "Overvoltage (OU)" or
"Undervoltage (LU)" active
142
Pulse inhibit
151
Quick stop is active
161
DC injection brake active
250
Warning active
C0184
*
Frequency
threshold
PCTRL1−I−OFF
0.0
0.0
{0.1 Hz}
25.0
l
If output frequency < C0184,
the I component of the process
controller is switched off
l
0.0 Hz = function inactive
^ 322
C0185
*
Switching
window for
"Frequency
setpoint
reached
(C0415/x = 4)"
and "NSET1−
RFG1−I=O
(C0415/x = 5)"
0
0
{1 %}
80
l
C0415/x = 4 and C0415/x = 5
are active within a window
which opens up around
NSET1−RFG1−IN
l
Window if C0185 = 0%:
± 0.5 % based on C0011
l
Window if C0185 > 0%:
± C0185 based on
NSET1−RFG1−IN
C0189
*
(A)
Output signal −
follow−up
controller
(PCTRL1−FOLL1−
OUT)
−650.00
{0.02
Hz}
650.00 Read only
Follow−up controller =
PCTRL1−FOLL1