Function library, Code table – Lenze E82xVxxxKxxxxx User Manual
Page 431
![background image](/manuals/566070/431/background.png)
Function library
Code table
l
431
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0430
*
v
(A)
Automatic
adjustment of
analog inputs
0
0
Inactive
The gain and offset are calculated
by entering two points of the
setpoint characteristic. Enter
points that are as far away from
each other as possible for high
accuracy of calculation:
1. In C0430, select the input the
gain and the offset are to be
calculated for
2. In C0431, enter the X value
(setpoint) and the Y value
(output frequency) of point 1
3. In C0432, enter the X value
(setpoint) and the Y value
(output frequency) of point 2
4. Calculated values are
automatically entered in C0413
(offset) and C0414 (gain)
^ 298
1
Entry of points for X3/1U, X3/1I
2
Entry of points for X3/2U, X3/2I
C0431
*
v
(A)
Coordinates of
point 1
−100.0
{0.1 %}
100.0
1 X (P1)
−100.0 Analog setpoint of P1
100 % = max. input value (5 V, 10 V or 20 mA)
2 Y (P1)
−100.0 Output frequency of P1
100 % = C0011
C0432
*
v
(A)
Coordinates of
point 2
−100.0
{0.1 %}
100.0
1 X (P2)
100.0 Analog setpoint of P2
100 % = max. input value (5 V, 10 V or 20 mA)
2 Y (P2)
100.0 Output frequency of P2
100 % = C0011
C0435
*
v
(A)
Automatic
adjustment of
frequency
input
0
0
= inactive
{1}
4096
l
Only required for speed control
with digital feedback via HTL
encoder
l
Calculates the gain C0426,
depending on C0425 and
C0011
l
C0426 is recalculated after
every change in C0011 or
C0425
l
Always enter the number of
increments divided by the
number of motor pole pairs!
– Example: number of encoder
increments = 4096, 4−pole
motor
Þ C0435 = 2048
C0440
(A)
Additional JOG
values
−650.00
{0.02
Hz}
650.00 JOG = fixed setpoint
Activation via configuration in
C0410
^ 309
1 JOG 1
20.00
C04401/1 and C0037 are the
same
2 JOG 2
30.00
C04401/2 and C0038 are the
same
3 JOG 3
40.00
C04401/3 and C0039 are the
same
4 JOG 4
15.00
5 JOG 5
25.00
6 JOG 6
35.00
7 JOG 7
45.00
C0469
*
s
Function of the
s key of the
keypad
1
0
Stop key without function
Determines the function to be
executed when the stop key is
pressed
l
s activates quick stop
l
U restarts the drive
Changes are only active after
mains connection!
1
CINH (controller inhibit)
2