Function library

Configuration of analog and digital setpoints and actual values
Setpoints via fixed setpoints (JOG)

10

l

310

EDS82EV903 EN 3.0

Active setpoint

Level at

NSET1−JOG1/3

NSET1−JOG2/3

Other setpoint source

LOW

LOW

JOG 1

HIGH

LOW

JOG 2

LOW

HIGH

JOG 3

HIGH

HIGH

)

Note!

In addition to the free configuration in C0410 you can also use the fixed
assignment in C0007 to link the function to digital inputs.

Operation with application I/O

ƒ

In C0410/1, link the NSET1−JOG1/3/5 signal to a digital input signal.

ƒ

In C0410/2, link the NSET1−JOG2/3/6/7 signal to a digital input signal.

ƒ

In C0410/33, link the NSET1−JOG4/5/6/7 signal to a digital input signal.

Active setpoint

Level at

NSET1−JOG1/3/5/7

NSET1−JOG2/3/6/7

NSET1−JOG4/5/6/7

Other setpoint source

LOW

LOW

LOW

JOG 1

HIGH

LOW

LOW

JOG 2

LOW

HIGH

LOW

JOG 3

HIGH

HIGH

LOW

JOG 4

LOW

LOW

HIGH

JOG 5

HIGH

LOW

HIGH

JOG 6

LOW

HIGH

HIGH

JOG 7

HIGH

HIGH

HIGH

Influence on other setpoints

ƒ

The maximum output frequency (C0011) also limits the fixed setpoints (JOG).

ƒ

The minimum output frequency (C0010) does not limit the fixed setpoints (JOG).

ƒ

Fixed setpoints (JOG) have priority over analog setpoint 1 (NSET1−N1) and analog
setpoint 2 (NSET1−N2).

ƒ

The additional setpoint (PCTRL1−NADD) acts additively on the fixed setpoints.

Setting tips

The display of the parameter can be related to a process variable. (

^ 362

)