Function library

Free interconnection of digital signals

Free configuration of digital outputs

10

l

353

EDS82EV903 EN 3.0

Switching conditions

Selection in C0415/x

Relay/digital output (not inverted)

1

Parameter set 2 or parameter set 4 is active
(DCTRL1−PAR−B0)

Increases/HIGH if parameter set 2 or 4 is
active

2

Pulse inhibit active (DCTRL1−IMP)

Increases/HIGH in case of

s, controller

inhibit (CINH), overvoltage or undervoltage

3

I

max

limit reached (MCTRL1−IMAX)

(C0014 = −5−: torque setpoint reached)

Increases/HIGH if motor current = C0022 or
motor current = C0023

4

Frequency setpoint reached (DCTRL1−RFG1=NOUT)

Increases/HIGH if output frequency =
frequency setpoint

5

Ramp function generator 1: input = output
(NSET1−RFG1−I=O)

Increases/HIGH if the condition is complied
with

6

Values have fallen below frequency threshold Q

min

(f < C0017) (PCTRL1−QMIN)

Increases/HIGH if the output frequency >
C0017 (based on setpoint)

7

Output frequency = 0 (DCTRL1−NOUT=0)

Increases/HIGH because

l

Frequency setpoint = 0 Hz, t

if

has expired

l

DC injection brake (DCB) active

l

Controller inhibited (CINH)

8

Controller inhibit active (DCTRL1−CINH)

Increases/HIGH if the controller is inhibited
due to

l

X3/28 = LOW

l

C0410/10 = active

l

s

13

Group signal (DCTRL1−OH−PTC−LP1−FAN1−WARN)
Overtemperature (

J

max

− 5 °C) (DCTRL1−OH−WARN)

or motor overtemperature (DCTRL1−LP1−PTC−WARN)
or motor phase failure (DCTRL1−LP1−WARN) or fan
failure (only active with 8200 motec)

Increases/HIGH if one of the messages is
active

14

DC bus overvoltage (DCTRL1−OV)

Increases/HIGH if the permissible voltage
threshold is reached

15

CCW rotation (DCTRL1−CCW)

Increases/HIGH in case of CCW rotation

16

Ready for operation (DCTRL1−RDY)

Increases/HIGH if the controller is ready for
operation
Decreases/LOW in case of

l

TRIP error message

l

Undervoltage or overvoltage

17

Parameter set 3 or parameter set 4 active
(DCTRL1−PAR−B1)

Increases/HIGH if parameter set 3 or 4 is
active

18

Values have fallen below TRIP or Q

min

or pulse

inhibit (IMP) is active (DCTRL1−TRIP−QMIN−IMP)

Decreases/LOW if at least one of the three
conditions (selection 25, 6 or 2) is complied
with

19

PTC warning (DCTRL1−PTC−WARN)

Decreases/LOW if thermal contact or PTC
reports motor overtemperature

20

Apparent motor current < current threshold
(DCTRL1−IMOT<ILIM)

Increases/HIGH if the condition is complied
with

21

Apparent motor current < current threshold and
output frequency > Frequency threshold Q

min

(DCTRL1−(IMOT<ILIM)−QMIN)

22

Apparent motor current < current threshold and
ramp function generator 1: input = output
(DCTRL1−(IMOT<ILIM)−RFG−I=0)

23

Motor phase failure warning (DCTRL1−LP1−WARN)

24

Min. output frequency reached (f

£ C0010)

(PCTRL1−NMIN)

Increases/HIGH if output frequency >
C0010

25

TRIP error message (DCTRL1−TRIP)

Increases/HIGH in case of TRIP error
message

26

Motor is running (DCTRL1−RUN)

Increases/HIGH if output frequency

¹ 0 Hz

27

Motor is running / CW rotation (DCTRL1−RUN−CW)

Increases/HIGH if output frequency > 0 Hz