Function library – Lenze E82xVxxxKxxxxx User Manual
Page 389
Function library
Code table
l
389
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0047
*
Torque
setpoint or
torque limit
(MCTRL1−
MSET)
400
0
{1 %}
400 The set value will be lost during
mains switching!
^ 264
Reference: Rated motor torque determined
through motor parameter identification
In "Sensorless torque control"
operating mode (C0014 = 5):
l
Torque setpoint selection if
C0412/6 = FIXED−FREE (not
assigned)
l
Torque setpoint display if
C0412/6 is linked to a signal
source
In "V/f characteristic control" or
"Vector control" operating mode
(C0014 = 2, 3, 4):
l
Display of the torque limit
value if C0412/6 is linked to a
signal source
l
Display C0047 = 400 if
C0412/6 = FIXED−FREE (not
assigned)
C0049
*
Additional
setpoint
(PCTRL1−NADD)
−650.00
{0.02
Hz}
650.00 The set value will be lost during
mains switching!
l
Selection if C0412/3 =
FIXED−FREE (not assigned)
l
Display if C0412/3 is linked to
a signal source
C0050
*
uSEr
Output
frequency
(MCTRL1−
NOUT)
−650.00
{Hz}
650.00 Read only: Output frequency
without slip compensation
C0051
*
Output freq.
with slip
compensation
(MCTRL1−NOUT
+SLIP) or
Actual process
controller
value
(PCTRL1−ACT)
−650.00
{0.02
Hz}
650.00 The set value will be lost during
mains switching!
During operation without process
controller (C0238 = 2):
l
Read only: output frequency
with slip compensation
(MCTRL1−NOUT+SLIP)
During operation with process
controller (C0238 = 0, 1):
l
Selection if C0412/5 =
FIXED−FREE (not assigned)
l
Display if C0412/5 is linked to
a signal source
^ 324
C0052
*
Motor voltage
(MCTRL1−VOLT)
0
{V}
1000 Read only
C0053
*
DC−bus voltage
(MCTRL1−
DCVOLT)
0
{V}
1000 Read only
C0054
*
Apparent
motor current
(MCTRL1−
IMOT)
0.0
{A}
2000.0 Read only
C0056
*
Device
utilisation
(MCTRL1−
MOUT)
−255
{%}
255 Read only
The display value for the "Vector
control" or "Sensorless torque
control" operating mode can be
changed in C0311.