background image

Commissioning

Parameter setting with the XT EMZ9371BC keypad

V/f characteristic control

8

l

209

EDS82EV903 EN 3.0

8.4

Parameter setting with the XT EMZ9371BC keypad

8.4.1

V/f characteristic control

The following instructions apply to controllers equipped with a standard−I/O function
module and a three−phase AC motor which has been selected according to a power−based
assignment.

Switch−on sequence

Comment

1.

Plug in the keypad

2.

Ensure that controller inhibit is active after mains
connection

misc001

20

28

X3

}

Terminal X3/28 = LOW

3.

Switch on the mains

ON

misc002

4.

After approx. 3 s the keypad is in the operating level
and displays the output frequency (C0050) and the
device utilisation (C0056)

9371BC004

d

A

B

b

c

0050

00

0.00 Hz

0 %

5.

For quick commissioning you select the "Quick
start" menu

d

A

B

b

c

p

SHPRG

Para

Code

Menu

4

2

Quick start

V / f q u i c k

9371BC007

The submenu "V/f quick" contains the
codes which you require for
commissioning a standard application.
The digital inputs are configured in the
Lenze setting:
X3/E1, X3/E2: activation of fixed
setpoints (JOG)
X3/E3: activation of DC injection brake
(DCB)
X3/E4: CW rotation/CCW rotation

A

Change the menu level with

V

B

Change to the "Quick start" menu and from there to
the submenu "V/f quick" with

z z Z z

C

Change to the code level with

Z to parameterise

your drive

Y Z

y

z

T V
S U

d

A

B

b

c

p

SHPRG

Para

Code

Menu

0034

00

0

A I N 1 r a n g e

9371BC008

6.

Adapt the voltage/current range for the analog
setpoint selection (C0034)
Lenze setting: 0, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)

Set the DIP switch on the standard I/O
to the same range (see Mounting
Instructions for the standard I/O)

7.

If required, adapt the fixed setpoints JOG.

A

JOG 1 (C0037)
Lenze setting: 20 Hz

Activation:
X3/E1 = HIGH, X3/E2 = LOW

B

JOG 2 (C0038)
Lenze setting: 30 Hz

Activation:
X3/E1 = LOW, X3/E2 = HIGH

C

JOG 3 (C0039)
Lenze setting: 40 Hz

Activation:
X3/E1 = HIGH, X3/E2 = HIGH

8.

Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz

0 %

[f]

100 %

C0011

C0010

9.

Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz

10.

Set the acceleration time T

ir

(C0012)

Lenze setting: 5.00 s

f [ H z ]

f 2

C 0 0 1 1

f 1

0

t i r

t i f

T i r

T i f

t

T

ir

+ t

ir

@

C0011

f2 * f1

t

ir

= desired acceleration time

11.

Set the deceleration time T

if

(C0013)

Lenze setting: 5.00 s

T

if

+ t

if

@

C0011

f2 * f1

t

if

= desired deceleration time