Function library – Lenze E82xVxxxKxxxxx User Manual
Page 323
Function library
Process controller
Select the setpoint source for the process controller
l
323
EDS82EV903 EN 3.0
Process controller setpoint = C0181
C0145 = 1
Process controller setpoint = Value under C0181.
ƒ
Applications are e.g. dancer controls, pressure controls and flow rate controls
ƒ
Activate the automatic DC−injection brake (auto DCB) with C0019 = 0 or C0106 = 0
ƒ
C0181 is the same in all parameter sets.
C0145 = 2
Process controller setpoint = Freely configured signal via C0412/4.
ƒ
The process controller setpoint (PCTRL1−SET1) must be linked with an analog input
signal under C0412/4.
ƒ
Use C0138 to display the current process controller setpoint.
ƒ
The setpoint acts directly on the process controller.
)
Note!
If you do not link an analog input signal with the process controller setpoint
under C0412/4, the process controller setpoint can be directly selected under
C0138.