Function library

Free interconnection of digital signals

Free configuration of digital input signals

10

l

347

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0411

v

Level inversion
− digital inputs

0

0

Level inversion switched off

l

By entering the sum of the
selected values you can invert
several inputs.

l

C0114 and C0411 are the same

l

The "Change over parameter
set" cannot be inverted!

1

E1 inverted

2

E2 inverted

4

E3 inverted

8

E4 inverted

16

E5 inverted

Only application I/O

32

E6 inverted

Only application I/O

64

T1/T2 inverted

Only connect potential−free
switches to T1/T2.
T1/T2 is active when the switch is
open.

Signal linkage

The internal digital signals are linked with an external signal source by entering the
selection figure of the external signal in the corresponding subcode of C0410. C0410 can
be different for the parameter sets.

Examples

ƒ

C0410/10 = 2

ð Terminal X3/E2 is the signal source for controller inhibit (CINH)

ƒ

C0410/15 = 32

ð CAN−IN1/word1, Bit 3 is the signal source for the DC injection

brake (DCB)

)

Note!

The process data input words CAN−IN1.W1, CAN−IN1.W2, CAN−IN2.W1 and
CAN−IN2.W2 can be defined as analog word or as digital word (16 bit). If you
link internal digital signals (C0410/x = 30 ... 105), they must be defined as
digital input words. Otherwise the controller would interpret the bit control
information incorrectly.

Signal level

ƒ

Terminals (X3/E1 ... X3/E6):
– HIGH = +12 V ... +30 V
– LOW = 0 V ... +3 V

ƒ

Process data input words:
– HIGH = bit logic 1
– LOW = bit logic 0

ƒ

Response times: 1.5 ... 2.5 ms