Electrical installation, Operation at rated power – Lenze E82xVxxxKxxxxx User Manual

Page 125

Advertising
background image

Electrical installation

Standard devices in a power range from 0.25 ... 2.2 kW

Fuses and cable cross−sections according to EN 60204−1

6

l

125

EDS82EV903 EN 3.0

Operation at rated power

8200 vector

Rated fuse current

Cable cross−section

ELCB

1)

Fuse

Circuit−breaker

Laying system L1, L2, L3, N, PE

B2

C

Type

[A]

[A]

[mm

2

]

[mm

2

]

[mA]

Mains 1/N/PE AC 230/240 V − operation without mains choke/mains filter

E82xV251K2C

10

C10

1.5

³ 30

E82xV371K2C

10

C10

1.5

E82xV551K2C

10

B10

1.5

E82xV751K2C

16

B16

2.5

4

)

E82xV152K2C

20

B20

2 x 1.5

E82xV222K2C

Operation only permitted with mains choke or mains filter

Mains 1/N/PE AC 230/240 V − operation with mains choke/mains filter

E82xV251K2C

10

C10

1.5

³ 30

E82xV371K2C

10

C10

1.5

E82xV551K2C

10

B10

1.5

E82xV751K2C

10

B10

1.5

E82xV152K2C

16

B16

2 x 1.5

E82xV222K2C

16

B16

2 x 1.5

Mains 3/PE AC 230/240 V − operation without mains choke/mains filter

E82xV551K2C

6

B6

1

³ 30

E82xV751K2C

6

B6

1

E82xV152K2C

16

B16

2 x 1.5

E82xV222K2C

20

B20

2 x 1.5

E82xV302K2C

16

B16

2.5

³ 300

2)

³ 30

3)

E82xV402K2C

20

B20

4

E82xV552K2C

B25

6

4

)

E82xV752K2C

B32

6

4

)

E82xV551K2C

6

B6

1

³ 30

E82xV751K2C

6

B6

1

E82xV152K2C

10

B10

1.5

E82xV222K2C

16

B16

2 x 1.5

Mains 3/PE AC 400/500 V − operation without mains choke/mains filter

E82xV551K4C

6

B6

1

³ 300

2)

³ 30

3)

E82xV751K4C

6

B6

1

E82xV152K4C

10

B10

1.5

E82xV222K4C

10

B10

1.5

Mains 3/PE AC 400/500 V − operation with mains choke/mains filter

E82xV551K4C

6

B6

1

³ 300

2)

³ 30

3)

E82xV751K4C

6

B6

1

E82xV152K4C

10

B10

1.5

E82xV222K4C

10

B10

1.5

1)

Earth−leakage circuit breaker

2)

Is used with E82EVxxxKxC0xx (with integrated EMC filter)

3)

Is used with E82EVxxxKxC2xx (without integrated EMC filter)

4)

Pin−end connector required

Advertising