Extensions for automation
Standard devices in a power range from 15 ... 90 kW
Mounting and dismounting function modules
l
185
EDS82EV903 EN 3.0
The following worksteps apply to the interfaces FIF I (at the top) and FIF II (at the bottom).
1. Disconnect the drive controller from mains and wait at least 3 minutes!
2. Carefully press the clip
0 upwards and remove the function module 1.
3. Remove the FIF cover
2.
4. Plug the function module
3 onto the terminals of the interface.
– Make sure that the pins of the FIF interface are plugged correctly in the sockets of
the function module and are not bent.
5. Push the blanking cover
3 until the clip 0 locks into place.
– Without the FIF cover
2, the controller is inhibited.
– If no function module is plugged on, the controller without FIF cover
2 and
blanking cover
1 must not be commissioned (dangerous electrical voltage at the
FIF interface).
)
Note!
ƒ
Keep the blanking cover
1 and the FIF protection cover 2 so that you can
attach them again after you have dismounted the function module.
– Without the FIF cover
2, the controller is inhibited.
– If no function module is plugged on, the controller without FIF cover
2 and
blanking cover
1 must not be commissioned (dangerous electrical voltage
at the FIF interface).
ƒ
When two function modules are operated, make sure that the two
terminals X3/28 (controller inhibit) of the interfaces FIF I and FIF II are
AND’ed internally and must be wired according to their
application.(
¶ 189).