Extensions for automation

Standard devices in a power range from 15 ... 90 kW

Mounting and dismounting function modules

7

l

185

EDS82EV903 EN 3.0

The following worksteps apply to the interfaces FIF I (at the top) and FIF II (at the bottom).

1. Disconnect the drive controller from mains and wait at least 3 minutes!
2. Carefully press the clip

0 upwards and remove the function module 1.

3. Remove the FIF cover

2.

4. Plug the function module

3 onto the terminals of the interface.

– Make sure that the pins of the FIF interface are plugged correctly in the sockets of

the function module and are not bent.

5. Push the blanking cover

3 until the clip 0 locks into place.

– Without the FIF cover

2, the controller is inhibited.

– If no function module is plugged on, the controller without FIF cover

2 and

blanking cover

1 must not be commissioned (dangerous electrical voltage at the

FIF interface).

)

Note!

ƒ

Keep the blanking cover

1 and the FIF protection cover 2 so that you can

attach them again after you have dismounted the function module.
– Without the FIF cover

2, the controller is inhibited.

– If no function module is plugged on, the controller without FIF cover

2 and

blanking cover

1 must not be commissioned (dangerous electrical voltage

at the FIF interface).

ƒ

When two function modules are operated, make sure that the two
terminals X3/28 (controller inhibit) of the interfaces FIF I and FIF II are
AND’ed internally and must be wired according to their
application.(

189).