Function library – Lenze E82xVxxxKxxxxx User Manual

Page 379

Advertising
background image

Function library

Code table

10

l

379

EDS82EV903 EN 3.0

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0001

v

Setpoint
selection
(operating
mode)

0

l

A change in C0001 triggers the
below−mentioned changes in
C0412 and C0410 if C0412 has
not been configured freely
before.

l

If C0412 has been configured
freely before (check: C0005 =
255), C0001 does not affect
C0412 and C0410. You must
link the signals manually.

l

Free configuration in C0412 or
C0410 does not affect C0001!

l

Control can be carried out via
terminals as well as via
PC/keypad.

^ 296

0

Setpoint selection via AIN1 (X3/8 or
X3/1U, X3/1I)

l

C0412/1 and C0412/2 are
linked to analog input 1
(C0412/1 = 1, C0412/2 = 1).

l

C0410 remains unchanged.

1

Setpoint selection via keypad or
parameter channel of an AIF bus
module

l

In C0412, the link to the analog
input is disconnected
(C0412/1 = 255,
C0412/2 = 255).

l

Setpoint selection via C0044 or
C0046.

l

C0410 remains unchanged.

2

Setpoint selection via AIN1 (X3/8 or
X3/1U, X3/1I)

l

C0412/1 and C0412/2 are
linked to analog input 1
(C0412/1 = 1, C0412/2 = 1).

l

C0410 remains unchanged.

3

Setpoint selection via process data
channel of an AIF bus module

l

C0001 = 3 must be set for the
setpoint selection via process
data channel of an AIF bus
module (types 210x, 211x,
213x, 217x)! Otherwise the
process data will not be
evaluated.

l

C0412/1 and C0412/2 are
linked to analog input words
AIF−IN.W1 and AIF−IN.W2
(C0412/1 = 10, C0412/2 = 11).

l

C0410/1 ... C0410/16 are
linked to the individual bits of
the AIF control word (AIF−CTRL)
(C0410/1 = 10 ... C0410/16 = 2
5).