Commissioning

Important codes for quick commissioning

8

l

219

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0013

uSEr

Deceleration
time main
setpoint

5.00

0.00

{0.02 s}

1300.00 Reference: frequency change

C0011... 0 Hz

l

Additional setpoint

ðC0221

l

Deceleration times that can be
activated via digital signals

ð

C0103

^ 286

C0014

v

Operating
mode

2

2

V/f characteristic control V ~ f
(linear characteristic with constant
V

min

boost)

l

Commissioning is possible
without identifying motor
parameters

l

Advantage of identification
with C0148:
– Improved smooth running at

low speeds

– V/f rated frequency (C0015)

and slip (C0021) are
calculated and saved. They do
not have to be entered

^ 255

3

V/f characteristic control V ~ f

2

(square−law characteristic with
constant V

min

boost)

4

Vector control

In the case of the first selection
enter the motor data and identify
them with C0148
Otherwise commissioning is not
possible
When C0014 = 5, C0019 must be
set = 0 (automatic DC injection
brake is deactivated)

5

Sensorless torque control with speed
limitation

l

Torque setpoint via C0412/6

l

Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum frequency
(C0011)

C0015

uSEr

V/f rated
frequency

50.00 7.50

{0.02

Hz}

960.00

l

C0015 is calculated and saved
during the motor parameter
identification with C0148.

l

The setting applies to all
permitted mains voltages

^ 205

^ 206

C0016

uSEr

V

min

boost

а

0.00

{0.01 %}

40.00

а

device−dependent

Setting applies to all permitted
mains voltages

^ 205

C0034
*

v

uSEr

Range of
setpoint
selection
Standard I/O
(X3/8)

Observe switch position of the
function module!

^ 298

0

0

Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA

1

Current 4 ... 20 mA

Reversal of rotation direction only
possible with a digital signal.

2

Bipolar voltage −10 V ... +10 V

l

Minimum output frequency
(C0010) not effective

l

Individually adjust offset and
gain

3

Current 4 ... 20 mA open−circuit
monitored

TRIP Sd5 if I < 4 mA
Reversal of rotation direction only
possible with a digital signal.

C0034
*

v

(A)

uSEr

Range of
setpoint
selection
Application I/O

Observe jumper position of the
function module!

^ 298

1 X3/1U, X3/1I

0

0

Unipolar voltage 0 ... 5 V / 0 ... 10 V

2 X3/2U, X3/2I

1

Bipolar voltage −10 V ... +10 V

Minimum output frequency
(C0010) not effective

2

Current 0 ... 20 mA

3

Current 4 ... 20 mA

Reversal of rotation direction only
possible with a digital signal.

4

Current 4 ... 20 mA open−circuit
monitored

Reversal of rotation direction only
possible with a digital signal.
TRIP Sd5 at I < 4 mA