Safety instructions – Lenze E82xVxxxKxxxxx User Manual

Page 26

Advertising
background image

Safety instructions

Safety instructions for the installation according to U

L

or U

R

3

l

26

EDS82EV903 EN 3.0

ƒ

E82xV302K2C ... E82xV752K2C (3.0 kW ... 7.5 kW, 240 V devices):
– Suitable for use on a circuit capable of delivering not more than 5000 rms

symmetrical amperes, 240 V maximum, when protected by fuses.

– Suitable for use on a circuit capable of delivering not more than 50000 rms

symmetrical amperes, 240 V maximum. When protected by CC, J, T or R
class fuses.

– Shall be installed in a Pollution Degree 2 macro−environment.
– Maximum surrounding air temperature: 0 ... +55 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.

ƒ

E82xV302K4C ... E82xV113K4C (3.0 kW ... 11 kW, 400/500 V devices):
– Suitable for use on a circuit capable of delivering not more than 5000 rms

symmetrical amperes, 500 V maximum, when protected by fuses or circuit
breakers (E82xV302K4C only).

– Suitable for use on a circuit capable of delivering not more than 50000 rms

symmetrical amperes, 500 V maximum. When protected by CC, J, T or R
class fuses

– Shall be installed in a Pollution Degree 2 macro−environment.
– Maximum surrounding air temperature: 0 ... +55 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.

ƒ

E82xV153K4B ... E82xV303K4B:
– Suitable for use on a circuit capable of delivering not more than 5000 rms

symmetrical amperes, 500 V maximum. When protected by fuses.

– Suitable for use on a circuit capable of delivering not more than 50000 rms

symmetrical amperes, 500 V maximum. When protected by J, T or R class
fuses

– Maximum surrounding air temperature: 0 ... +50 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.

ƒ

E82xV453K4B ... E82xV903K4B:
– Suitable for use on a circuit capable of delivering not more than 10000 rms

symmetrical amperes, 500 V maximum. When protected by fuses.

– Suitable for use on a circuit capable of delivering not more than 50000 rms

symmetrical amperes, 500 V maximum. When protected by J, T or R class
fuses

– Maximum surrounding air temperature: 0 ... +50 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.