Electrical installation, Realisation – Lenze E82xVxxxKxxxxx User Manual
Page 132
![background image](/manuals/566070/132/background.png)
Electrical installation
Standard devices in a power range from 3 ... 11 kW
EMC−compliant wiring
l
132
EDS82EV903 EN 3.0
Realisation
M
3~
L < 500 mm
L < 40 mm
1
2
3
4
5
6
7
8
9
0
PES
PES
PE
PE
PE
PES
8200vec066
Fig. 6−12
Wiring in compliance with EMC standards
0
Mounting plate with electrically conductive surface
1
Control cable to the function module, connect the shielding to the EMC shield sheet (PES) with
a surface as large as possible
2
2−pole terminal for motor PE and motor shield
3
PE of the motor cable
4
Shield of the motor cable
5
Shielded motor cable, low−capacitance
(Core/core 1.5 mm
2
£ 75 pF/m; from 2.5 mm
2
£ 100 pF/m; core/shield £ 150 pF/m)
6
Shielded PTC cable or thermal contact cable
7
Connect the cable shields to the EMC shield sheet (PES) with a surface as large as possible. Use
the supplied shield clamps.
8
Star or delta connection as indicated on the motor nameplate
9
EMC cable connector (not included in the delivery package)