4 mains chokes for dc-bus operation, 4 mains chokes for dc−bus operation, Dc−bus operation – Lenze E82xVxxxKxxxxx User Manual
Page 465
DC−bus operation
Mains chokes for DC−bus operation
l
465
EDS82EV903−3.0
12.4
Mains chokes for DC−bus operation
)
Note!
In the DC−bus operation, mains chokes must be connected upstream to every
feeding point to ensure trouble−free operation. Mains filters can be used if
their inductance corresponds to the inductance of the specified mains choke.
The mains chokes specified in the tables refer to the load of the feeding point
during rated operation. They do not apply to the operation with increased
rated power.
8200 vector frequency inverter
Inverter
Mains
Mains chokes required for the feeding points
Type
Voltage
Rated current
Type
Inductance
Rated current
[A]
[mH]
[A]
E82xV551K2C
3/PE, 230 V
2.7
EZN3A0900H004
9.0
4.0
E82xV751K2C
3.6
E82xV152K2C
6.3
EZN3A0300H013
3.0
13.0
E82xV222K2C
9.0
Inverter
Mains
Mains chokes required for the feeding points
Type
Voltage
Rated current
Type
Inductance
Rated current
[A]
[mH]
[A]
E82xV302K2C
3/PE, 230 V
12.0
EZN3A0300H013
3.0
13.0
E82xV402K2C
16.0
ELN3−0120H017
1.2
17.0
E82xV552K2C
21.0
ELN3−0150H024
1.5
24.0
E82xV752K2C
28.0
ELN3−0088H035
0.88
35.0
Inverter
Mains
Mains chokes required for the feeding points
Type
Voltage
Rated current
Type
Inductance
Rated current
[A]
[mH]
[A]
E82xV551K4C
3/PE, 400 V
2.0
ELN3−1500H003−001
15.0
2.5
E82xV751K4C
2.3
E82xV152K4C
3.9
ELN3−0680H006−001
6.8
6.1
E82xV222K4C
5.1
ELN3−0500H007−001
5.0
7.0
E82xV302K4C
7.0
E82xV402K4C
8.8
ELN3−0250H013−001
2.5
13.0
E82xV552K4C
12.0
E82xV752K4C
15.0
ELN3−0150H024−001
1.5
24.0
E82xV113K4C
21.0