4 mains chokes for dc-bus operation, 4 mains chokes for dc−bus operation, Dc−bus operation – Lenze E82xVxxxKxxxxx User Manual

Page 465

Advertising
background image

DC−bus operation

Mains chokes for DC−bus operation

12

l

465

EDS82EV903−3.0

12.4

Mains chokes for DC−bus operation

)

Note!

In the DC−bus operation, mains chokes must be connected upstream to every
feeding point to ensure trouble−free operation. Mains filters can be used if
their inductance corresponds to the inductance of the specified mains choke.
The mains chokes specified in the tables refer to the load of the feeding point
during rated operation. They do not apply to the operation with increased
rated power.

8200 vector frequency inverter

Inverter

Mains

Mains chokes required for the feeding points

Type

Voltage

Rated current

Type

Inductance

Rated current

[A]

[mH]

[A]

E82xV551K2C

3/PE, 230 V

2.7

EZN3A0900H004

9.0

4.0

E82xV751K2C

3.6

E82xV152K2C

6.3

EZN3A0300H013

3.0

13.0

E82xV222K2C

9.0

Inverter

Mains

Mains chokes required for the feeding points

Type

Voltage

Rated current

Type

Inductance

Rated current

[A]

[mH]

[A]

E82xV302K2C

3/PE, 230 V

12.0

EZN3A0300H013

3.0

13.0

E82xV402K2C

16.0

ELN3−0120H017

1.2

17.0

E82xV552K2C

21.0

ELN3−0150H024

1.5

24.0

E82xV752K2C

28.0

ELN3−0088H035

0.88

35.0

Inverter

Mains

Mains chokes required for the feeding points

Type

Voltage

Rated current

Type

Inductance

Rated current

[A]

[mH]

[A]

E82xV551K4C

3/PE, 400 V

2.0

ELN3−1500H003−001

15.0

2.5

E82xV751K4C

2.3

E82xV152K4C

3.9

ELN3−0680H006−001

6.8

6.1

E82xV222K4C

5.1

ELN3−0500H007−001

5.0

7.0

E82xV302K4C

7.0

E82xV402K4C

8.8

ELN3−0250H013−001

2.5

13.0

E82xV552K4C

12.0

E82xV752K4C

15.0

ELN3−0150H024−001

1.5

24.0

E82xV113K4C

21.0