Commissioning

Parameter setting with the XT EMZ9371BC keypad
V/f characteristic control

8

l

210

EDS82EV903 EN 3.0

Comment

Switch−on sequence

12.

Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz

100%

0

0

C0015

V

min

V

out

f

13.

Set the V

min

boost (C0016)

Lenze setting: depends on the controller type

The Lenze setting is suitable for all
common applications

14.

Activate the motor temperature monitoring (C0119)
if you have connected a PTC or thermal contact to
terminal X2.2
Lenze setting: switched off

Possible settings

(

220)

When all settings are complete:

15.

Select setpoint

E.g. via potentiometer at
terminals 7, 8, 9

16.

Enable the controller

20

28

X3

misc002

Terminal X3/28 = HIGH

17.

The drive is now running.

If the drive does not start, additionally
press

u

)

Note!

In the "Diagnostic" menu you can monitor the most important drive
parameters