Commissioning – Lenze E82xVxxxKxxxxx User Manual
Page 210
![background image](/manuals/566070/210/background.png)
Commissioning
Parameter setting with the XT EMZ9371BC keypad
V/f characteristic control
l
210
EDS82EV903 EN 3.0
Comment
Switch−on sequence
12.
Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz
100%
0
0
C0015
V
min
V
out
f
13.
Set the V
min
boost (C0016)
Lenze setting: depends on the controller type
The Lenze setting is suitable for all
common applications
14.
Activate the motor temperature monitoring (C0119)
if you have connected a PTC or thermal contact to
terminal X2.2
Lenze setting: switched off
Possible settings
(
¶ 220)
When all settings are complete:
15.
Select setpoint
E.g. via potentiometer at
terminals 7, 8, 9
16.
Enable the controller
20
28
X3
misc002
Terminal X3/28 = HIGH
17.
The drive is now running.
If the drive does not start, additionally
press
u
)
Note!
In the "Diagnostic" menu you can monitor the most important drive
parameters