Technical data – Lenze E82xVxxxKxxxxx User Manual

Page 42

Advertising
background image

Technical data

Operation with rated power (normal operation)
Rated data for 400 V mains voltage

4

l

42

EDS82EV903 EN 3.0

Typical motor power −
three−phase asynchronous
motor (4−pole)

P

rated

[kW]

45

55

P

rated

[hp]

60

75

8200 vector type

With mains filter

E82xV453K4B3xx

E82xV553K4B3xx

Without mains filter

E82xV453K4B2xx

3)

E82xV553K4B2xx

3)

Rated mains current at a
switching frequency of 8 kHz
(Lenze setting)

without mains choke/mains

filter

I

mains

[A]

With mains choke/mains filter

I

mains

[A]

80

100

Output power +U

DC

, −U

DC

1)

P

DCres

[kW]

5.1

0

Rated output
current at
switching
frequency

1 kHz sin

I

r

[A]

89

110

2 kHz sin

4 kHz sin

8 kHz sin

I

r

[A]

59

4)

76

4)

16 kHz sin

2)

I

r

[A]

46

60

1 kHz

I

r

[A]

89

110

2 kHz

4 kHz

8 kHz

I

r

[A]

89

110

16 kHz

2)

I

r

[A]

54

77

Max. permissible
output current for
60 s at switching
frequency

1 kHz sin

I

max

[A]

134

165

2 kHz sin

4 kHz sin

8 kHz sin

I

max

[A]

88

4)

114

4)

16 kHz sin

2)

I

max

[A]

69

78

1 kHz

I

max

[A]

134

165

2 kHz

4 kHz

8 kHz

I

max

[A]

134

165

16 kHz

2)

I

max

[A]

81

100

Power loss (operation with I

N8

)

E82EV...

P

loss

[W]

1100

1470

E82DV... inside/outside

P

loss

[W]

367/733

490/980

E82CV... inside/cooler

P

loss

[W]

Dimensions

Dependent on the mounting variant (

^ 61)

Mass with mains
filter

E82EV...

m [kg]

60

66

E82DV...

m [kg]

60

66

E82CV...

m [kg]

Mass without
mains filter

E82EV...

m [kg]

36

38

E82DV...

m [kg]

36

38

E82CV...

m [kg]

1)

Power supplied by the DC bus when operating with power−adapted motor

2)

Switching frequency is reduced to 4 kHz if

J reaches max. − 5 °C

3)

Operation only permitted with mains choke (

^ 106)

4)

Only operate with automatic switching frequency reduction (C144 = 1). Ensure that the specified current values are
not exceeded.

Advertising