Function library – Lenze E82xVxxxKxxxxx User Manual
Page 256
![background image](/manuals/566070/256/background.png)
Function library
Operating mode
l
256
EDS82EV903 EN 3.0
Recommended operating modes for standard applications
The following table helps you to select the appropriate mode of operation for standard
applications:
Application
Operating mode
Single drives
Setting in C0014
recommended
alternatively
With strongly alternating loads
4
2
With a high starting duty
4
2
With speed control (speed feedback)
2
4
With a high dynamic performance (e.g. positioning and infeed drives)
2
−
With a torque setpoint
5
−
With torque limitation (power control)
2
4
Three−phase reluctance motors
2
−
Three−phase sliding rotor motors
2
−
Three−phase AC motors with a fixedly assigned frequency−voltage
characteristic
2
−
Pump and fan drives with a square−law load characteristic
3
2 or 4
Group drives
(several motors connected to one controller)
Equal motors and equal loads
2
−
Different motors and/or alternating loads
2
−
C0014 = 2: linear V/f characteristic control
C0014 = 3: square−law V/f characteristic control
C0014 = 4: vector control
C0014 = 5: sensorless torque control
)
Note!
ƒ
Only change between the operating modes if the controller is inhibited!
ƒ
Do not use the operating mode "Torque control" for applications with
power control!
ƒ
Optimum drive behaviour in process controller applications, e.g. with speed
control or dancer position control can be achieved with the control modes
"linear V/f characteristic control" or with "vector control".
– If you need a high torque at low speed we recommend the operating mode
vector control".