Function library

Parameter set management

Saving and copying parameter sets

10

l

371

EDS82EV903 EN 3.0

Saving your own basic setting

1. Attach keypad.

2. Parameter set 1 must be active!

3. Inhibit controller with

s or via terminal (X3/28 = LOW).

4. Set parameter in parameter set 1.

5. Set C0003 = 3 and confirm with

v.

6. Set C0002 = 9 and confirm with

v. The own basic setting is saved.

7. Set C0003 = 1 and confirm with

v.

Copying your own basic setting into the parameter sets

1. Attach keypad.

2. Inhibit controller with

s or via terminal (X3/28 = LOW).

3. Set the correct selection number in C0002 from the "Loading/saving your own basic

setting" category and confirm with

v.

– E.g. C0002 = 5: Parameter set 1 is overwritten with your own basic setting.
– E.g. C0002 = 8: Parameter set 4 is overwritten with your own basic setting.