Function library – Lenze E82xVxxxKxxxxx User Manual
Page 371
![background image](/manuals/566070/371/background.png)
Function library
Parameter set management
Saving and copying parameter sets
l
371
EDS82EV903 EN 3.0
Saving your own basic setting
1. Attach keypad.
2. Parameter set 1 must be active!
3. Inhibit controller with
s or via terminal (X3/28 = LOW).
4. Set parameter in parameter set 1.
5. Set C0003 = 3 and confirm with
v.
6. Set C0002 = 9 and confirm with
v. The own basic setting is saved.
7. Set C0003 = 1 and confirm with
v.
Copying your own basic setting into the parameter sets
1. Attach keypad.
2. Inhibit controller with
s or via terminal (X3/28 = LOW).
3. Set the correct selection number in C0002 from the "Loading/saving your own basic
setting" category and confirm with
v.
– E.g. C0002 = 5: Parameter set 1 is overwritten with your own basic setting.
– E.g. C0002 = 8: Parameter set 4 is overwritten with your own basic setting.