Process controller

Set control loop properties

10

l

319

EDS82EV903 EN 3.0

Pressure control and flow control

ƒ

The differential component K

D

(C0072) is generally not required for pressure and

flow control.

ƒ

Set the influence (C0074) to 100 %.

ƒ

Deactivate the frequency feedforward control (C0238 = 0).

Code

Setting for

Gases

Fluids

C0070 (K

P

)

0.1

0.02 ... 0.1

C0071 (T

N

)

5000 (T

N

= 5 s)

200 ... 1000 (T

N

= 0.2 s ... 1 s)

C0072 (K

D

)

0

0

Speed control

Code

Setting

C0070 (K

P

)

5

C0071 (T

N

)

100 (T

N

= 0.1 s)

C0072 (K

D

)

0

Set the influence of the process controller

ƒ

Activate frequency feedforward control (C0238 = 1). Now the process controller has
only limited influence:
– The control factor determines the influence of the process controller (C0074).
– Control factor = C0050 (output frequency) − C0051 (actual process controller value)

ƒ

C0074 refers to the maximum output frequency C0011.

ƒ

C0074 influences the stability of the control loop:
– Set C0074 as low as possible.
– If C0074 is set too high, the control loop can become unstable.

Calculate the influence of the process controller

Calculate C0074

Example

C0074 [%] + C0050 * C0051

C0011

@ 100 %

C0011 = 50 Hz, C0050 = 53 Hz, C0051 = 50 Hz:

C0074 [%] + 53 Hz * 50 Hz

50 Hz

@ 100 % + 6 %

Set the influence so that the process controller output covers the calculated value in every
working point.

Set C0074 = 10 % as guide value for the example (C0074 = 6 %). The guide value contains
tolerances which must always be observed.