Dc−bus operation – Lenze E82xVxxxKxxxxx User Manual
Page 468
DC−bus operation
Fuses and cable cross−sections
Mains supply
l
468
EDS82EV903−3.0
8200 vector
Rated fuse current
Cable cross−section
Fuse
Circuit−breaker
Laying system L1, L2, L3, PE
B2
C
Type
[A]
[A]
[mm
2
]
[mm
2
]
Mains 3/PE AC 230/240 V − operation with mains choke/mains filter
E82xV551K2C
−
C6
1.0
1,0
E82xV751K2C
−
C6
1.0
1,0
E82xV152K2C
16
C16
2 x 1.5
2 x 1.5
E82xV222K2C
16
C16
2 x 1.5
2 x 1.5
E82xV302K2C
20
C20
4.0
2.5
E82xV402K2C
25
C25
6.0
1)
4.0
E82xV552K2C
−
C32
−
6.0
1)
E82xV752K2C
−
C32
−
6.0
1)
Mains 3/PE AC 400/500 V operation with mains choke/mains filter
E82xV551K4C
−
C6
1.0
1.0
E82xV751K4C
−
C6
1.5
1.0
E82xV152K4C
−
C10
1.5
1.0
E82xV222K4C
−
C10
1.5
1.0
E82xV302K4C
20
C20
4.0
2.5
E82xV402K4C
20
C20
4.0
2.5
E82xV552K4C
20
C20
4.0
2.5
E82xV752K4C
32
C32
−
6.0
1)
E82xV113K4C
32
C32
−
6.0
1)
E82xV153K4B
80
−
−
25
E82xV223K4B
80
−
−
25
E82xV303K4B
80
−
−
25
E82xV453K4B
160
−
−
70
E82xV553K4B
160
−
−
70
E82xV753K4B
250
−
−
120
E82xV903K4B
250
−
−
120
1)
Pin−end connector required, since a maximum cable cross−section of 4 mm
2