IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0111

v

(cont.)

Configuration
of analog
output X3/62
(AOUT1−IN)

21

Apparent motor current < current
threshold (DCTRL1−IMOT<ILIM)

V−belt monitoring
Apparent motor current = C0054
Current threshold = C0156
Frequency threshold Q

min

= C0017

^ 332

22

Apparent motor current < current
threshold and output frequency >
Frequency threshold Q

min

(DCTRL1−(IMOT<ILIM)−QMIN)

23

Apparent motor current < current
threshold and ramp function generator
1: input = output
(DCTRL1−(IMOT<ILIM)−RFG−I=0)

24

Motor phase failure warning
(DCTRL1−LP1−WARN)

25

Min. output frequency reached
(f

£ C0010) (PCTRL1−NMIN)

LOW active

255

Free configuration in C0419/1

Read only
Do not change C0111 since
settings in C0419/1 may get lost

C0114

v

Level inversion
− digital inputs

0

0

Level inversion switched off

l

By entering the sum of the
selected values you can invert
several inputs.

l

C0114 and C0411 are the same

l

The "Change over parameter
set" cannot be inverted!

1

E1 inverted

2

E2 inverted

4

E3 inverted

8

E4 inverted

16

E5 inverted

Only application I/O

32

E6 inverted

Only application I/O

64

T1/T2 inverted

Only connect potential−free
switches to T1/T2.
T1/T2 is active when the switch is
open.

C0117

v

Fixed
configuration −
digital output
A1 (DIGOUT1)

0

Change of C0117 is copied to
C0415/2. Free configuration in
C0415/2 sets C0117 = 255!

^ 348

0 ... 16

See C0008

255

Free configuration in C0415/2

Read only
Do not change C0117 since
settings in C0415/2 may get lost

C0119

v

Configuration
of motor
temperature
monitoring
(PTC input) /
earth fault
detection

0

0

PTC input inactive

Earth fault
detection active

l

Configure signal output in
C0415

l

If several parameter sets are
used, monitoring has to be set
separately for every parameter
set.

l

Deactivate earth fault
detection if the earth fault
detection is actuated
unintentionally.

l

If the earth fault detection is
activated, the motor starts
with a delay of approx. 40 ms
after controller enable has
been set.

^ 359

1

PTC input active,
TRIP effected

2

PTC input active,
warning effected

3

PTC input inactive

Earth fault
detection inactive

4

PTC input active,
TRIP effected

5

PTC input active,
warning effected

C0120 I

2

t switch−off

0

0
= inactive

{1 %}

200 Reference: apparent motor

current (C0054)
Reference to active motor current
(C0056) possible, see C0310

^ 357