Function library
Code table
l
393
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0111
v
(cont.)
Configuration
of analog
output X3/62
(AOUT1−IN)
21
Apparent motor current < current
threshold (DCTRL1−IMOT<ILIM)
V−belt monitoring
Apparent motor current = C0054
Current threshold = C0156
Frequency threshold Q
min
= C0017
^ 332
22
Apparent motor current < current
threshold and output frequency >
Frequency threshold Q
min
(DCTRL1−(IMOT<ILIM)−QMIN)
23
Apparent motor current < current
threshold and ramp function generator
1: input = output
(DCTRL1−(IMOT<ILIM)−RFG−I=0)
24
Motor phase failure warning
(DCTRL1−LP1−WARN)
25
Min. output frequency reached
(f
£ C0010) (PCTRL1−NMIN)
LOW active
255
Free configuration in C0419/1
Read only
Do not change C0111 since
settings in C0419/1 may get lost
C0114
v
Level inversion
− digital inputs
0
0
Level inversion switched off
l
By entering the sum of the
selected values you can invert
several inputs.
l
C0114 and C0411 are the same
l
The "Change over parameter
set" cannot be inverted!
1
E1 inverted
2
E2 inverted
4
E3 inverted
8
E4 inverted
16
E5 inverted
Only application I/O
32
E6 inverted
Only application I/O
64
T1/T2 inverted
Only connect potential−free
switches to T1/T2.
T1/T2 is active when the switch is
open.
C0117
v
Fixed
configuration −
digital output
A1 (DIGOUT1)
0
Change of C0117 is copied to
C0415/2. Free configuration in
C0415/2 sets C0117 = 255!
^ 348
0 ... 16
See C0008
255
Free configuration in C0415/2
Read only
Do not change C0117 since
settings in C0415/2 may get lost
C0119
v
Configuration
of motor
temperature
monitoring
(PTC input) /
earth fault
detection
0
0
PTC input inactive
Earth fault
detection active
l
Configure signal output in
C0415
l
If several parameter sets are
used, monitoring has to be set
separately for every parameter
set.
l
Deactivate earth fault
detection if the earth fault
detection is actuated
unintentionally.
l
If the earth fault detection is
activated, the motor starts
with a delay of approx. 40 ms
after controller enable has
been set.
^ 359
1
PTC input active,
TRIP effected
2
PTC input active,
warning effected
3
PTC input inactive
Earth fault
detection inactive
4
PTC input active,
TRIP effected
5
PTC input active,
warning effected
C0120 I
2
t switch−off
0
0
= inactive
{1 %}
200 Reference: apparent motor
current (C0054)
Reference to active motor current
(C0056) possible, see C0310
^ 357