6 connection of relay output, Connection of relay output, Electrical installation – Lenze E82xVxxxKxxxxx User Manual

Page 140

Advertising
background image

Electrical installation

Standard devices in a power range from 3 ... 11 kW
Connection of relay output

6

l

140

EDS82EV903 EN 3.0

6.5.6

Connection of relay output

8200vec061

Fig. 6−16

Relay connection 3 ... 11 kW

Function

Relay position

(activated)

Message

(Lenze setting)

Technical data

X1.2/K11 Relay output

normally−closed contact

opened

TRIP

AC 250 V/3 A
DC 24 V/2 A ... DC 240 V/0.16 A

X1.2/K12 Relay mid−position

contact

X1.2/K14 Relay output

normally−open contact

closed

TRIP

PES

HF shield termination by PE connection through shield clamp

)

Note!

ƒ

Switching of control signals:
– Use shielded cables
– HF shield termination by PE connection
– The minimum load for switching the signals through correctly is 12 V and

5 mA. Both values have to be exceeded at the same time.

ƒ

Switching of mains potentials:
– Unshielded cables are sufficient

ƒ

For the protection of the relay contacts a corresponding suppressor circuit is
absolutely required for an inductive or a capacitive load!

ƒ

The service life of the relay depends on the type of load (ohmic, inductive or
capacitive) and the value of the switching capacity.

ƒ

The message that is output can be changed in code C0008 or C0415/1.