Function library

Code table

10

l

399

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0155

*

Extended
status word

Bit

Assignment

0

Not ready for operation (NOT
DCTRL−RDY)

1

not assigned

2

I

max

(MCTRL1−IMAX)

3

Pulse inhibit (DCTRL1−IMP)

4

not assigned

5

Controller inhibit (DCTRL1−CINH)

6

TRIP (DCTRL1−TRIP)

7

not assigned

8

Group signal
(DCTRL1−OH−PTC−LP1−FAN1−WARN)

9

PAR B0 (DCTRL1−PAR−B0)

10

PAR B1 (DCTRL1−PAR−B1)

11 ... 15 Reserved

C0156
*

Current
threshold

0

0

{1 %}

150 Programmable current threshold

l

Based on rated controller
current

l

Configure signal output in
C0008 or C0415

l

In C0311 the reference variable
for the "Vector control" and
"Sensorless speed control"
operating mode can be
changed (from software
version 3.1).

C0161
*

Active fault

Display of history buffer contents

l

Keypad: three−digit
alphanumeric fault
identification

l

Operating module 9371BB:
LECOM error number

^ 453

C0162
*

Last fault

C0163
*

Last fault but
one

C0164
*

Last fault but
two

C0165 Service code

LECOM

Alterations by Lenze service only!

C0168
*

Pending error

Display of history buffer "Active
fault"

l

Keypad: three−digit
alphanumeric fault
identification

l

Operating module 9371BB:
LECOM error number

^ 453

C0170

v

Configuration
of TRIP reset

0

0

TRIP reset by mains switching,

s,

LOW edge at X3/28, via function
module or communication module

l

TRIP reset via function module
or communication module
with C0043, C0410/12 or
C0135 bit 11

l

Auto TRIP reset automatically
resets all faults after the time
in C0171 has elapsed

^ 459

1

Like 0 and additionally auto TRIP reset

2

TRIP reset by mains switching, via
function module or communication
module

3

TRIP reset by mains switching

C0171 Delay for auto

TRIP reset

0.00

0.00

{0.01 s}

60.00