2 technical data, Technical data, Extensions for automation – Lenze E82xVxxxKxxxxx User Manual
Page 197: 2 technical data operating conditions, Connection data
![background image](/manuals/566070/197/background.png)
Extensions for automation
I/O function module E82ZAFACO10 (application I/O PT)
Technical data
l
197
EDS82EV903 EN 3.0
7.5.2
Technical data
Operating conditions
Ambient conditions
Climate
Storage
IEC/EN 60721−3−1
1K3 (−25 to +60 °C)
Transport
IEC/EN 60721−3−2
2K3 (−25 to +70 °C)
Operation
Corresponding to the data of the Lenze standard device used (see documentation
of the standard device).
Pollution
EN 61800−5−1
Degree of pollution 2
Connection data
X3.1/
1U/2U
1I/2I
Temperature error (0...+60°C) for level (based on actual value):
l
0 ... +5 V:
l
0 ... +10 V:
l
−10 ... +10 V:
l
0/+4 ... +20 mA:
1 %
0.6 %
0.6 %
0.6 %
Linearity distortion:
±
0.5 %
A/D converter:
Resolution: 10 bits,
Error (based on the final value): 1 digit
º
0.1 %
Input resistance: voltage signal: > 50 k
W
, current signal: 250
W
X3.2/
62
63
Resolution: 10 bits
Linearity distortion (based on the actual value):
±
0.5 %
Temperature error (0...+60 °C): 0.6 %
Load capacity (0 ... +10 V): I
max
= 2 mA
Load resistance (0/+4 ... +20 mA):
£
500
W
9
Load capacity: I
max
= 5 mA
X3.3/
A1
A2
Load capacity:
l
I
max
= 10 mA, with internal supply
l
I
max
= 50 mA, with external supply
A4
Load capacity: I
max
= 8 mA
f = 50 Hz ...10 kHz
20
Load capacity:
S
I
max
= 60 mA
28
Input resistance: 3.2
kW
1 = HIGH (+12 ... +30 V), PLC level, HTL
0 = LOW (0 ... +3 V), PLC level, HTL
E1
1)
E2
1)
E3
E4
E5
E6
1)
optionally frequency input 0 ... 102.4 kHz (one−track or two−track), configuration via C0425