Function library, Code table – Lenze E82xVxxxKxxxxx User Manual
Page 390
Function library
Code table
l
390
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0061
*
Heatsink
temperature
0
{
°C}
255 Read only
l
If the heatsink temperature
>
J
max
− 5 °C:
– Warning OH is provided
– Switching frequency is
reduced to 4 kHz if C0144 = 1
l
If the heatsink temperature
>
J
max
:
– Controller sets TRIP OH
C0070 Process
controller gain
1.00
0.00
= P component
inactive
{0.01}
300.00
^ 318
C0071 Process
controller reset
time
100
10
{1}
9999
= I component
inactive
^ 318
C0072 Differential
component −
process
controller
0.0
0.0
= D component
inactive
{0.1}
5.0
^ 318
C0074 Influence of
the process
controller
0.0
0.0
{0.1 %}
100.0
^ 318
C0077
*
Gain of the
I
max
controller
0.25
0.00
= P component
inactive
{0.01}
16.00
^ 327
C0078
*
Reset time of
the I
max
controller
65
à
13
0
12
{1 ms}
9990
= I component
inactive
à
Only 8200 vector 15 ... 90 kW)
^ 327
C0079 Oscillation
damping
2
0
{1}
140
^ 272
C0080 Service code
Alteration by Lenze service only!
C0084 Motor stator
resistance
0.000 0.000
{0.001
W}
64.000
^ 315
0.0
0.0
{0.1
m
W}
6500.0 Only 8200 vector 15 ... 90 kW
C0087 Rated motor
speed
à
300
{1 rpm}
16000
à
Device−dependent
^ 315
C0088 Rated motor
current
à
0.0
0.1 (A)
650.0
à
Device−dependent
0.0 ... 2.0 x rated output current of
the controller
^ 315
C0089 Rated motor
frequency
50
10
{1 Hz}
960
^ 315
C0090 Rated motor
voltage
à
50
{1 V}
500
à
230 V for 230 V controllers,
400 V for 400 V controllers
^ 315
C0091 Motor cos
ϕ
а
0.40
{0.1}
1.0
а
Device−dependent
^ 315
C0092 Motor stator
inductance
0.0
0.000
{0.1 mH} Device−dependent
^ 315
0.00
0.00
{0.01
mH}
Device−dependent Only 8200 vector 15 ... 90 kW
C0093
*
Device type
xxxy
Read only
l
xxx = performance data from
the type code (e.g. 551 = 550
W)
l
y = voltage class (2 = 240 V,
4 = 400 V)
C0094
*
User password
0
= no password
protection
{1}
9999 1 ... 9999 = free access to the user
menu only
^ 231