Function library

Configuration of analog and digital setpoints and actual values
Analog setpoints via terminal

10

l

302

EDS82EV903 EN 3.0

Inverse setpoint selection

f

C0011

Deadband

Offset=

-100

%,

gain

= -100

%

Of

fset

>

-100

%,

gain

<

-100

%

Offset

< -100

%,

gain

> -100

%

5 V
10 V
20 mA
10 kHz

0 V
0 mA
0 kHz

Setpoint
signal

8200vec531

Fig. 10−10

Gain and offset at inverse setpoint selection

Example of inverse setpoint selection

A dead band of +2 V (= 20 %) is to be set for an inverse setpoint selection (0 ... +10 V). The
output frequency is to be inverted with an increasing setpoint signal and is to reach −30 %
at setpoint +10 V.

f

C0011

(100 %)

Deadband

P1

P2

+ 10 V

(100 %)

+ 2 V

(20 %)

0 V

(0 %)

-30 %

Setpoint
signal

8200vec532

Fig. 10−11

Calculation example for gain and offset

Gain calculation

Gain [%] +

f (P

2

) * f (P

1

)

U (P

2

) * U (P

1

) @ 100 % +

* 30 % * 100 %

100 % * 20 % @ 100% + * 162.5 %

Offset calculation

Offset (P

2

) [%] +

f (P

2

) [%]

Gain [%] @ 100 % * U (P

2

) [%] + * 30 %

* 162.5 % @ 100 % * 100 % + * 81.5 %