4 operation with rated power (normal operation), 1 rated data for a mains voltage of 230 v, Operation with rated power (normal operation) – Lenze E82xVxxxKxxxxx User Manual
Page 32: Rated data for a mains voltage of 230 v, Technical data
![background image](/manuals/566070/32/background.png)
Technical data
Operation with rated power (normal operation)
Rated data for a mains voltage of 230 V
l
32
EDS82EV903 EN 3.0
4.4
Operation with rated power (normal operation)
4.4.1
Rated data for a mains voltage of 230 V
Basis of the data
AC mains connection
1/N/PE
U
r
180 V − 0 % ... 264 V + 0 %; 45 Hz − 0 % ... 65 Hz + 0 %
3/PE
DC−mains connection
(alternatively)
U
DC
DC 260 V − 0 % ... 370 V + 0 %
Output voltage
With mains choke
V
M
3 ~ 0 ... approx. 94 % U
mains;
0 ... 650 Hz
without mains choke
V
M
3 ~ 0 ... U
mains;
0 ... 650 Hz
Periodic load change
60 s overcurrent with I
max
and 120 s base load with 75 % I
rated
Typical motor power
Three−phase asynchronous
motor (4−pole)
P
rated
[kW]
0.25
0.37
P
rated
[hp]
0.33
0.5
8200 vector type
EMC filter integrated
E82xV251K2C0xx
E82xV371K2C0xx
Without EMC filter
E82xV251K2C2xx
E82xV371K2C2xx
Mains
1/N/PE
1/N/PE
Rated mains current at a
switching frequency of 8 kHz
(Lenze setting)
without mains choke
I
mains
[A]
3.4
5.0
With mains choke
I
mains
[A]
3.0
4.2
Output power +U
DC
, −U
DC
1)
P
DCres
[kW]
DC−bus system not possible
Rated output
current at
switching
frequency
2 kHz sin
I
r
[A]
1.7
2.4
4 kHz sin
8 kHz sin
I
r
[A]
1.7
2.4
16 kHz sin
2)
I
r
[A]
1.1
1.6
Max. permissible
output current for
60 s at switching
frequency
2 kHz sin
I
max
[A]
2.5
3.6
4 kHz sin
8 kHz sin
I
max
[A]
2.5
3.6
16 kHz sin
2)
I
max
[A]
1.7
2.3
Power loss (operation with I
N8
)
E82EV...
P
loss
[W]
30
40
E82DV... inside/outside
P
loss
[W]
10/20
13/27
E82CV... inside/cooler
P
loss
[W]
10/20
13/27
Dimensions
Dependent on the mounting variant (
^ 61)
Mass
E82EV...
m [kg]
0.8
0.8
E82DV...
m [kg]
0.8
0.8
E82CV...
m [kg]
0.6
0.6
1)
Power supplied by the DC bus when operating with power−adapted motor
2)
Switching frequency is reduced to 4 kHz if
J reaches max. − 5 °C