7 central supply (one supply point), 1 central supply via external dc source, Central supply via external dc source – Lenze E82xVxxxKxxxxx User Manual

Page 478: Dc−bus operation, Stop

Advertising
background image

DC−bus operation

Central supply (one supply point)
Central supply via external DC source

12

l

478

EDS82EV903−3.0

12.7

Central supply (one supply point)

One central feeding point is used to supply the DC−bus system of the controllers via +U

G

,

−U

G

.

DC−bus system

Possible supply sources

230 V controller

A DC source

400 V controller

l

A DC source

l

A regenerative power supply module

l

A controller with reserve power

12.7.1

Central supply via external DC source

Basic circuit diagram

A1

U

V W

-UG +UG

A2

U

V W

-UG +UG

F5

+

-

F5

PE

F4

F4

+

L2

L1

L3

L2

L1

L3

+

8200vec654

Fig. 12−3

Network of 230 V controllers with central supply via external DC source

A1, A2

230 V controller of the 8200 vector series

F4, F5

Fuses on DC level (

470)

(

Stop!

Please observe for trouble−free DC−bus operation:

ƒ

General measures (

460)

ƒ

For 400 V controller: The voltage curve +U

G

® PE / −U

G

® PE must be

symmetrical. Controllers are destroyed if +U

G

or −U

G

are earthed.