Mechanical installation
Standard devices in the power range 15 ... 30 kW
Mounting in "cold plate" technique
l
83
EDS82EV903−3.0
5.4.3
Mounting in "cold plate" technique
For this mounting variant you require the controller type E82CV...
The following points are important for safe and reliable operation of the controller:
ƒ
Good thermal connection to the cooler
– The contact surface between the collective cooler and the controller must be at
least as large as the cooling plate of the controller.
– Plane contact surface, max. deviation 0.05 mm.
– When attaching the collective cooler to the controller, make sure to use all
specified screw connections.
ƒ
Observe the thermal resistance R
th
given in the table. The values are valid for
controller operation under rated conditions.
Power to be dissipated by the heatsink
Cooling path of heatsink − ambience
8200 vector
P
v
[W]
R
th
[K/W]
СССССС
СССССС
E82CV153K4B
СССССССССССС
СССССССССССС
287
ССССССССССССС
ССССССССССССС
£ 0.085
СССССС
E82CV223K4B
СССССССССССС
427
ССССССССССССС
£ 0.057
Ambient conditions
ƒ
The rated data and the derating factors at increased temperature also apply to the
ambient temperature of the drive controllers.
ƒ
Temperature at the cooling plate of the drive controller: max. 75 °C.