Function library

Limit value setting

Current limits

10

l

285

EDS82EV903 EN 3.0

C0023 = 30 %

At V/f characteristic control the current−limit controller is not active for the operation in
generator mode with C0023 = 30%:

ƒ

Possibly reasonable in applications with medium frequency asynchronous motors if
motor and generator mode cannot be detected as fault−free.

ƒ

Drive behaviour in case of motor and generator overload (C0054 > C0022):
– The controller reduces the output frequency to 0 Hz.
– The controller cancels the change of the output frequency if the load falls below

the limit value.