Function library

Free interconnection of digital signals
Free configuration of digital process data output words

10

l

356

EDS82EV903 EN 3.0

Signal linkage

The process data output words are linked with internal signals by entering the selection
figure of the internal signal in the corresponding subcode C0417 and C0418. C0417 and
C0418 can be different for the parameter sets.

Examples

ƒ

C0417/4

ð 16: The status message Ready for operation" is the signal source for bit

3.

ƒ

C0418/5

ð 101: Bit 2 of CAN−IN2.W1 is the signal source for bit 4.

)

Note!

The process data output words CAN−OUT1.W1/FIF−OUT.W1, CAN−OUT2.W1
and FIF−OUT.W2 can also be assigned as analog word under C0421:

ƒ

If digitally configured under C0417 or C0418 no simultaneous analog
assignment with C0421 (C0421/x = 255)!

ƒ

With analog configuration under C0421 no simultaneous digital assignment
with C0417 and C0418 (C0417/x = 255, C0418/x = 255)!

ƒ

Otherwise the status information would be incorrect.