Function library – Lenze E82xVxxxKxxxxx User Manual

Page 365

Advertising
background image

Function library

Display of operating data, diagnostics

Display of operating data

10

l

365

EDS82EV903 EN 3.0

Calibration

The calibrated value can be calculated from:

C0xxx + C0011

200 @

C0500

C0501

Example of calibration

The pressure setpoint is selected in bar.

The maximum pressure of 5 bar (100 %) is reached if C0011 = 50 Hz.

Relative calibration in %

100 % + 50

200 @

C0500

C0501 +

50

200 @

4000

10

Solution with e.g. C0500 = 4000, C0501 = 10

Absolute calibration in bar

5.00 bar + 50

200 @

C0500

C0501 +

50

200 @

200

10

Solution with e.g. C0500 = 200, C0501 = 10

)

Note!

During operation with standard I/O, frequency−related codes such as C0010,
C0011, C0017, C0019, C0050, C0239, C0625, C0626 and C0627 are also
displayed in the unit defined through calibration.