Function library – Lenze E82xVxxxKxxxxx User Manual
Page 365
Advertising
![background image](/manuals/566070/365/background.png)
Function library
Display of operating data, diagnostics
Display of operating data
l
365
EDS82EV903 EN 3.0
Calibration
The calibrated value can be calculated from:
C0xxx + C0011
200 @
C0500
C0501
Example of calibration
The pressure setpoint is selected in bar.
The maximum pressure of 5 bar (100 %) is reached if C0011 = 50 Hz.
Relative calibration in %
100 % + 50
200 @
C0500
C0501 +
50
200 @
4000
10
Solution with e.g. C0500 = 4000, C0501 = 10
Absolute calibration in bar
5.00 bar + 50
200 @
C0500
C0501 +
50
200 @
200
10
Solution with e.g. C0500 = 200, C0501 = 10
)
Note!
During operation with standard I/O, frequency−related codes such as C0010,
C0011, C0017, C0019, C0050, C0239, C0625, C0626 and C0627 are also
displayed in the unit defined through calibration.