Technical data – Lenze E82xVxxxKxxxxx User Manual
Page 35
![background image](/manuals/566070/35/background.png)
Technical data
Operation with rated power (normal operation)
Rated data for a mains voltage of 230 V
l
35
EDS82EV903 EN 3.0
Typical motor power
Three−phase asynchronous
motor (4−pole)
P
rated
[kW]
3.0
4.0
P
rated
[hp]
4.0
5.0
8200 vector type
EMC filter integrated
E82xV302K2C0xx
E82xV402K2C0xx
Without EMC filter
E82xV302K2C2xx
E82xV402K2C2xx
Mains
3/PE
3/PE
Rated mains current at a
switching frequency of 8 kHz
(Lenze setting)
without mains choke
I
mains
[A]
15.6
21.3
with mains choke
I
mains
[A]
12.0
16.0
Output power +U
DC
, −U
DC
1)
P
DCres
[kW]
0.9
0.8
Rated output
current at
switching
frequency
2 kHz sin
I
r
[A]
12.0
16.5
4 kHz sin
8 kHz sin
I
r
[A]
12.0
16.5
16 kHz sin
2)
I
r
[A]
7.8
10.7
Max. permissible
output current for
60 s at switching
frequency
2 kHz sin
I
max
[A]
18.0
24.8
4 kHz sin
8 kHz sin
I
max
[A]
18.0
24.8
16 kHz sin
2)
I
max
[A]
11.7
16.1
Power loss (operation with I
N8
)
E82EV...
P
loss
[W]
150
190
E82DV... inside/outside
P
loss
[W]
50/100
63/127
E82CV... inside/cooler
P
loss
[W]
50/100
63/127
Dimensions
Dependent on the mounting variant
(
^ 61
)
Mass
E82EV...
m [kg]
2.9
E82DV...
m [kg]
2.9
E82CV...
m [kg]
2.4
1)
Power supplied by the DC bus when operating with power−adapted motor
2)
Switching frequency is reduced to 4 kHz if
J reaches max. − 5 °C