Extensions for automation

I/O function module E82ZAFSCO10 (Standard I/O PT)

Installation

7

l

195

EDS82EV903 EN 3.0

Analog input configuration

1

ON

2 3 4 5

ON

OFF

)

Note!

ƒ

Make sure to set the DIP switch and C0034 to the same range, otherwise the
analog input signal at X3/8 will be interpreted incorrectly by the basic
device.

ƒ

If a setpoint potentiometer is supplied internally via X3/9, make sure to set
the DIP switch to the voltage range 0 ... 5 V. Otherwise it will be impossible
to cover the entire speed range.

Signal at X3/8

Switch position

C0034

1

2

3

4

5

0 ... 5V

OFF

OFF

ON

OFF

OFF

0

0 ... 10 V (Lenze setting)

OFF

OFF

ON

OFF

ON

0

0 ... 20 mA

OFF

OFF

ON

ON

OFF

0

4 ... 20 mA

OFF

OFF

ON

ON

OFF

1

4 ... 20 mA (open−circuit monitored)

OFF

OFF

ON

ON

OFF

3

−10 ... +10 V

ON

ON

OFF

OFF

OFF

2